Analog I/O Slave Unit (input) Functions
11-4-10 Cumulated Count
Description
526
Note
8. Click the Close Button to close the Adjustment Window.
9. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
10. Click the OK Button and exit the window.
The cumulated count calculates an approximation to the integral of analog
input values over time. The cumulated value can be calculated in “count
hours” (by selecting “hours”) or “count minutes” (by selecting “minutes”). The
count value is the analog input value in the industry unit obtained after scal-
ing. For example, 100.0 count hours indicates a value equivalent to an analog
input value of 100 counts continuing for one hour. The counter range for a
four-byte area (two words) for count hours or count minutes is –214,748,364.8
to 214,748,364.7. Data is displayed on the CX-Integrator in units of 0.1 hour
or minute.
Monitor values can be set in the Slave Unit. When the cumulated count value
exceeds the set monitor value, the Cumulated Counter Flag in the area for
Generic Status Flags turns ON.
The following table shows the divisions for the cumulated counter.
Analog input value
Hour
Minute
To return the set value to the default setting, click the Default Setting But-
ton.
download the data, and then click the Reset Button to reset the Unit.
Unit
Division width (See note.)
3.6 s (1/1,000 hour)
60 ms (1/1,000 minute)
Cumulated value
(count × hour or count × minute)
Divisions
Time
Section 11-4