T1611100 Red Lion Controls, T1611100 Datasheet - Page 23

PID TEMPERATURE CONTROLLER, 3RELAYS

T1611100

Manufacturer Part Number
T1611100
Description
PID TEMPERATURE CONTROLLER, 3RELAYS
Manufacturer
Red Lion Controls
Type
Temperaturer
Datasheets

Specifications of T1611100

Thermocouple Type
T, E, J, K, R, S, B, N, C, Linear MV
Operating Temperature Max
50°C
Operating Temperature Min
0°C
Output Voltage Max
250VAC
Output Voltage Min
30VDC
Accuracy
0.3%
Approval
RoHS Compliant
Brand/series
T16 Series
Contact Form
SPST
Dimensions
49.5mmW×49.5mmH×115.3mmD
Enclosure Rating
IP65
Input Type
RTD/Thermocouple
Ip Rating
IP65
Memory
EEPROM
Mounting Type
Panel
Output Type
Relay
Power, Rating
8 VA
Primary Type
Controller
Special Features
EEPROM
Standards
cURus, CE
Termination
Screw
Voltage, Supply
85 to 250 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
PID Adjustments
calculated PID parameters. To do this, a chart recorder or data logging device is
needed to provide a visual means of analyzing the process. Compare the actual
process response to the PID response figures with a step change to the process.
Make changes to the PID parameters in no more than 20% increments from the
starting value and allow the process sufficient time to stabilize before evaluating
the effects of the new parameter settings.
MANUAL TUNING
between process cycles. This procedure is an alternative to the controller’s Auto-
Tune function. It will not provide acceptable results if system problems exist.
1. Set the Proportional Band (ProP) to 10.0% for temperature models (T16) and
2. Set both the Integral Time (Intt) and Derivative Time (dErt) to 0 seconds.
3. Set the Output Dampening Time (OPdP) in Output Module 2-OP to 0 seconds.
4. Set the Output Cycle Time [CYCt] in Output Module 2-OP to no higher than
5. Place the controller in Manual USEr Control Mode trnF in the Hidden Loop
6. Place the controller in Automatic (Auto) Control Mode trnF in the Hidden
In some applications, it may be necessary to fine tune the Auto-Tune
A chart recorder or data logging device is necessary to measure the time
100.0% for process models (P16).
one-tenth of the process time constant (when applicable).
and adjust the % Power to drive the process value to the Setpoint value.
Allow the process to stabilize after setting the % Power. Note: trnF must be
set to HidE in Parameter Lockouts Module 3-LC.
Loop. If the process will not stabilize and starts to oscillate, set the
Proportional Band two times higher and go back to Step 5.
PROCESS RESPONSE EXTREMES
23
control results or induced oscillations may cause system problems. In these
applications, Manual Tuning is an alternative.
7. If the process is stable, decrease Proportional Band setting by two times and
8. Fix the Proportional Band to three times the setting that caused the oscillation
9. Set the Integral Time to two times the period of the oscillation.
10. Set the Derivative Time to 1/8 (0.125) of the Integral Time.
11. Set the Output Dampening Time to 1/40 (0.025) the period of the oscillation.
In some unusual cases, the Auto-Tune function may not yield acceptable
change the Setpoint value a small amount to excite the process. Continue
with this step until the process oscillates in a continuous nature.
in Step 7.

Related parts for T1611100