C500BC031 Omron, C500BC031 Datasheet - Page 72

no-image

C500BC031

Manufacturer Part Number
C500BC031
Description
BACKPLANE
Manufacturer
Omron
Datasheet

Specifications of C500BC031

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
C120 (3G2A6) Host Link Units
C120 and C500
Minimum response time =
56
Minimum Response Time
Buffer for Host
Link Unit # 0
PC for Host
Link Unit # 0
Buffer for Host
Link Unit # 31
PC for Host
Link Unit # 31
Input
signal
Output
signal
Host computer
CPU reads
input signal
Input ON delay
Input ON delay + Command transmission time + Cycle time of PC for Unit #0 + Response transmission
time + Host computer processing time + Command transmission time + Output ON delay
Command/response for Unit # 0
Command
I/O refresh
Cycle time
Although the C120 and C500 equations for the minimum and maximum re-
sponse times are the same as those for the C1000H and C2000H, the break-
down of the CPU’s cycle differs. These groups are thus treated in different sec-
tions.
The data flow that will produce the minimum response time is shown below. This
flow assumes that all signals and data transmissions are processed as soon as
they occur. The equation for the minimum response time is given below the dia-
gram.
Response
I/O response time
Cycle time
Host computer
processing time
Host link service
Command/response for Unit # 31
Command
Overseeing
Cycle time
Host link service
Response
output signal
CPU writes
Cycle time
Output ON delay
I/O refresh
Section 2-3

Related parts for C500BC031