990XCP98000 SQUARE D, 990XCP98000 Datasheet - Page 442

no-image

990XCP98000

Manufacturer Part Number
990XCP98000
Description
QUANTUM CPU BATTERY FOR S
Manufacturer
SQUARE D
Datasheet

Specifications of 990XCP98000

Rohs Compliant
YES
Battery Capacity
1800mAh
Battery Technology
Lithium
Battery Voltage
3V
Battery Terminals
Connector
Weight
0.12lb
10
1
2
3
4
5
6
7
8
9
Standards and
certifications
Temperature
Relative humidity
Altitude
Characteristics
Operating conditions and requirements relating to the environment
10/2
Operation
Storage
Operation
Storage
°C
°C
%
%
m
Modicon
automation platform
Standards, certifications and
environmental conditions
Modicon Quantum PLCs have been developed to comply with the main national and
international standards relating to electronic equipment for industrial automation
systems.
b
safety, etc.: IEC 61131-2, CSA 22.2 No. 142, UL 508.
b
GL, LR, RINA, etc.
b
v
v
b
UL 746C, UL 94.
b
v
v
b
v
v
Modicon Quantum PLCs comply with “TC” treatment requirements (climate
treatments).
For installations in industrial production workshops or environments that correspond
to “TH” treatment (treatment for hot and humid environments), the PLCs must be
incorporated in casings with at least IP 54 protection, as specified by IEC 60664 and
NF C 20 040.
These PLC themselves have an IP 20 protection index (2).
They can therefore be installed without casings in reserved access areas that do not
exceed pollution level 2 (control room containing no machinery or activity that
produces dust). Pollution level 2 does not take account of harsher environments:
air polluted with dust, fumes, corrosive or radioactive particles, vapors or salts,
moulds, insects, etc.
(1) TSX P57 0244/104/154M and TSX P57 454/4634/554/5634M CPUs: 0…+57°C
(2) If a slot is not occupied by a module, it must be fitted with a protective cover TSX RKA 02.
Standards and certifications
0...+60 (IEC 61131-2: +5...+55) (1)
-40...+85
0…95 non-condensing
0…95 non-condensing (according to IEC 61131-2) at 60°C (140°F)
0…5000 max. during operation. For altitudes > 2000 m, the max. temperature of 60°C must be
reduced by 6°C for each additional 1000 m
Protective treatment of Modicon Quantum PLCs
Requirements specific to PLCs: functional characteristics, immunity, resistance,
Merchant navy requirements from the main international bodies: ABS, BV, DNV,
Compliance with European Directives:
Low voltage: 2006/95/EC
Electromagnetic compatibility: 2004/108/EC
Electrical characteristics and self-extinguishing capacity of insulating materials:
Hazardous areas:
CSA 22.2 No. 213, Class I, Division 2, groups A, B, C and D
FM 3610, Class I, Division 2, groups A, B, C and D
Specific requirements for safety CPUs and modules:
IEC 61508
IEC 62021
(or 0…+67°C with TSX FAN fan modules) when certain I/O modules are mounted in the slot
next to the above-mentioned CPUs.
®
Quantum