Presentation
4/46
Modicon
automation platform
Analog I/O modules
The Modicon Quantum automation platform offers a complete range of analog I/O
modules designed to interface with a wide variety of devices. These modules comply
with internationally accepted IEC electrical standards that help ensure their reliability
in harsh environments. For increased protection and extended life in extremely
harsh environments, these modules can be ordered with a special treatment.
All Quantum I/O modules can be configured using Unity Pro
ProWORX
software makes it easy to add or change modules in the configuration, without
having to change the application program.
Analog modules frequently require the specification of particular parameters for
various functions. The ability of the Quantum platform to configure multifunction
modules via the software eliminates the need for selection using miniswitches or
complex programming. A software function, called I/O Map zoom, provides access to
a configuration screen where the operational parameters of the module can be
initialized or modified. This zoom technique is used on multifunction analog input
modules, fast counters, single-axis motion control modules or temperature
measurement modules using thermocouples or RTDs.
The Quantum platform gives you the ability to predefine how an analog output
channel will behave in the event of a fault, when the module stops being controlled
for any reason. The outputs can be configured in the software so that they will:
b
b
b
The behavior in the event of a fault can be defined for each channel. If the module is
changed, the individually defined states in the event of faults are sent to the
replacement module.
Optionally, primary mechanical keying pins can be inserted between the I/O module
and its screw terminal block to help ensure that the correct connector/module pairing
is used. These primary keying pins are unique to each type of module. Secondary
mechanical keying pins can be used on a rack containing identical modules, with the
same primary keying pin, to help ensure correct connector/module pairings. The
keying pins are supplied with each I/O module.
Each I/O module requires a 140 XTS 002 00 I/O connector, to be ordered separately.
Intrinsically safe I/O modules do not use this connector.
The “Grounding and Electromagnetic Compatibility of PLC Systems. Basic Principles and
Measures. User Manual” no. 33002439 provides helpful information on setting up Modicon
Quantum PLCs in accordance with the directives and legal regulations in force in the
European Union and North America.
Presentation
Fully software-configurable
I/O Map zoom function
Definition of the behavior of the output modules in the event of a fault
Mechanical keying pins
I/O connectors
Change to state 0
Go to a predefined safe state
Maintain the value they had at the time of the fault.
software. The ability to assign the I/O addresses of the modules in the
®