C500TS502 Omron, C500TS502 Datasheet - Page 61

no-image

C500TS502

Manufacturer Part Number
C500TS502
Description
RTD INPUT MODULE
Manufacturer
Omron
Datasheet

Specifications of C500TS502

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Number of RTD inputs
Input signal range
Intelligent functions
Resolution
Accuracy
Conversion time
Reporting data format
Number of I/O channels
PLC communications
Internal memory
Front window indicators
Input connector
Vibration resistance
Impact resistance
Isolation
Power consumption
Dimensions
Weight
p
p
g
g
Durability
Malfunction 10 to 61.2 Hz at 0.1 mm amplitude in X, Y and Z directions for 4
Durability
Malfunction 20 G in X, Y and Z directions three times each direction
8 channels, isolated
10 Ω Copper -100 to 260°C, -148 to 500°F
100 Ω Platinum -200 to 850°C, -328 to 1562°F
120 Ω Nickel -80 to 260°C, -112 to 500°F
Scaling, alarming, averaging, filtering, peak hold. Selectable and
configurable per input point
1° in BCD, 0.1° in binary
±1°C, ±2°F
15 msec for all inputs
Signed BCD
2’s Complement binary
Configurable from CV or serial port
2 or 4 (jumper selectable)
Intelligent I/O read/write instructions for OMRON C, CV, CVM1
series
RAM
EEPROM for memory map storage
Run, error, range, comm error, transmit/receive
32 point terminal block
10 to 54.8 Hz at 0.25 mm amplitude in X, Y and Z directions for 12
sweeps in 10 min.
54.8 to 300 Hz at 3G in X, Y and Z directions for 12 sweeps in 10
min.
sweeps in 8 min.
61.2 to 150 Hz acceleration at 1.5 G in X, Y and Z directions for 4
sweeps in 8 min.
30 G in X, Y and Z directions three times each direction
Optical isolation between input terminals and PLC: 1500 VAC
Optical isolation for RS-232C: 500 VAC
1.3 A from backplane; 6.2 W max.
34.5(W) x 250(H) x 127(D)
700 g maximum
Specifications
APPENDIX B
55

Related parts for C500TS502