C500TS502 Omron, C500TS502 Datasheet - Page 17

no-image

C500TS502

Manufacturer Part Number
C500TS502
Description
RTD INPUT MODULE
Manufacturer
Omron
Datasheet

Specifications of C500TS502

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Setting RTD Input Range
3- -2
Setting RTD Input Range
The C500-TS502 RTD Input Module is initially set at the factory to a 100 Ω
Platinum Type. This module can be set to 3 different RTD types. Setting input
ranges is accomplished with jumpers and rotary switches. The following chart
indicates the RTD input ranges.
To set the various input ranges for each input point, proceed as follows.
1.
2.
1 = 10 Ω Copper
2 = 100 Ω Platinum
3 = 120 Ω Nickel
Rotary
switches
100 Ω Platinum
10 Ω Copper
120 Ω Nickel
For existing installations, remove the module from the backplane to gain
access to the rotary switches, otherwise proceed to step 2.
Remove the terminal block cover at the front of the module.
Type
RTD Input Ranges
-101 to +260
-201 to +851
-81 to +260
Terminal
block cover
Captive
screw
°C
-330 to +1564
-149 to +500
-114 to +500
Jumpers
°F
10 Ω Copper
100 Ω Platinum
120 Ω Nickel
3 wire
4 wire
2 wire
Front of
module
Section 3- -2
Terminal
connectors
Circuit
board
11

Related parts for C500TS502