3UG4622-1AW30 SIEMENS, 3UG4622-1AW30 Datasheet - Page 9

RELAY, MONITOR, 22.5MM

3UG4622-1AW30

Manufacturer Part Number
3UG4622-1AW30
Description
RELAY, MONITOR, 22.5MM
Manufacturer
SIEMENS
Series
3UG46r
Datasheet

Specifications of 3UG4622-1AW30

Contact Configuration
SPCO
Power Consumption
4VA
Supply Voltage Max
240VAC
Contact Current Max
3A
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
230V
External Depth
86mm
Coil Frequency Max
60Hz
Coil Operating Frequency Min
50Hz
Expansion with a ground fault measuring module with an
external summation current transformer
Instead of ground fault monitoring using the current measuring
modules or current/voltage measuring modules, it may be
necessary, especially in high-impedance grounded networks, to
implement ground fault monitoring for smaller ground fault
currents using a summation current transformer. A ground fault
module can be used to add an additional input to basic unit 2 for
connection of a summation current transformer (3UL2 20.-.A).
Maximum one ground fault module can be connected to one
basic unit 2.
3UF7 500-1AA00-0 ground fault module
1 input for connecting a summation current transformer
(3UL2 20.-.A)
1 Ready LED
2 system interfaces for connection
• To basic unit 2
• Of expansion modules
• Of a current measuring module or current/voltage measuring
• Of an operator panel
Note:
A ground fault module can only be used with a basic unit 2,
product version E02 and later (from April 2005).
module
SIMOCODE 3UF Motor Management and Control Devices
Expansion of analog temperature monitoring with a
temperature module
Independently of the thermistor motor protection of the basic
units, up to 3 analog temperature sensors can be evaluated
using a temperature module.
The temperatures measured here can be completely integrated
in the process, monitored and supplied to a higher-level
automation system. The temperature module can be used, for
example, for analog monitoring of the temperature of the motor
windings or bearings or for monitoring the coolant or gear oil
temperature. Various sensor types are supported (resistance
sensors) for use in solid, liquid or gaseous media:
• PT100/PT1000
• KTY83/KTY84
• NTC
Maximum one temperature module can be connected to one
basic unit 2. The same sensor type must be used in all sensor
measuring circuits.
3UF7 700-1AA00-0 temperature module
3 inputs for connecting up to 3 resistance sensors in 2-wire or
3-wire circuits
1 Ready LED
2 system interfaces for connection
• To basic unit 2
• Of expansion modules
• Of a current measuring module or current/voltage measuring
• Of an operator panel
Note:
A temperature module can only be used with a basic unit 2,
product version E02 and later (from April 2005).
module
motor management and control devices
Siemens LV 1 T · 2006
SIMOCODE pro 3UF7
7/9

Related parts for 3UG4622-1AW30