3UG4622-1AW30 SIEMENS, 3UG4622-1AW30 Datasheet - Page 64

RELAY, MONITOR, 22.5MM

3UG4622-1AW30

Manufacturer Part Number
3UG4622-1AW30
Description
RELAY, MONITOR, 22.5MM
Manufacturer
SIEMENS
Series
3UG46r
Datasheet

Specifications of 3UG4622-1AW30

Contact Configuration
SPCO
Power Consumption
4VA
Supply Voltage Max
240VAC
Contact Current Max
3A
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
230V
External Depth
86mm
Coil Frequency Max
60Hz
Coil Operating Frequency Min
50Hz
3UG Monitoring Relays for Electrical and Additional Measurements
Line monitoring
3UG45 13 monitoring relays
The 3UG45 13 line monitoring relay monitors three-phase
networks with regard to phase sequence, phase failure, phase
unbalance of 20 % and undervoltage. The device has an internal
power supply and works using the closed-circuit principle. The
hysteresis is 5 %. The integrated response delay time is
adjustable from 0 to 20 s and responds to undervoltage. If the
direction is incorrect, the device switches off immediately.
Thanks to a special measuring method, a phase failure is reliably
detected in spite of the wide voltage range from 160 to 690 V AC
and feedback through the load of up to 80 %. When the mains
supply is switched on, the green LED is lit. If the phase
sequence at the terminals L1-L2-L3 is correct, the output relay
picks up. If the phase sequence is wrong, the red LED flashes
and the output relay remains in its rest position. If a phase fails,
the red LED is permanently lit and the output relay drops.
Note:
The red LED is a fault diagnostic indicator and does not show the
current relay status. The 3UG45 13 monitoring relay is suitable
for line frequencies of 50/60 Hz.
Phase failure and undervoltage
Wrong phase sequence
L3-L2-L1
11/14
11/12
21/24
21/22
LED rd
LED rd
7/64
11/14
11/12
21/24
21/22
3~U
L1-L2-L3
n
OFF
Monitoring Relays
Phase sequence
OFF
Siemens LV 1 T · 2006
FLASH
L2-L3
Phase loss
ON
OFF
L1-L2-L3
Delay
OFF
-20%
ON
OFF
NSB0_01569
Hysteresis
5%
3UG46 14 monitoring relays
The 3UG46 14 line monitoring relay has a wide voltage range
and an internal power supply. The device is equipped with a
display and is parameterized using three buttons. It monitors
three-phase networks with regard to phase unbalance from 5 to
20 %, phase failure, undervoltage and phase sequence. The
hysteresis is adjustable from 1 to 20 V. In addition, the device
has a response delay and ON delay from 0 to 20 s in each case.
The integrated response delay time responds to phase
unbalance and undervoltage. If the direction is incorrect, the
device switches off immediately. Thanks to a special measuring
method, a phase failure is reliably detected in spite of the wide
voltage range from 160 to 690 V AC and feedback through the
load.
The 3UG46 14 monitoring relay can be operated on the basis of
either the open-circuit or closed-circuit principle and with
manual or auto RESET.
With the closed-circuit principle selected
Wrong phase sequence
Phase failure
Undervoltage
Unbalance
L3-L2-L1
11/14
11/12
21/24
21/22
11/14
11/12
21/24
21/22
11/14
11/12
21/24
21/22
x-y
11/14
11/12
21/24
21/22
0%
onDelay
onDelay
L1-L2-L3
L2-L3
> Asy
<
Delay
Delay
L1-L2-L3
Hysteresis
Hysteresis
2%