3UG4622-1AW30 SIEMENS, 3UG4622-1AW30 Datasheet - Page 102

RELAY, MONITOR, 22.5MM

3UG4622-1AW30

Manufacturer Part Number
3UG4622-1AW30
Description
RELAY, MONITOR, 22.5MM
Manufacturer
SIEMENS
Series
3UG46r
Datasheet

Specifications of 3UG4622-1AW30

Contact Configuration
SPCO
Power Consumption
4VA
Supply Voltage Max
240VAC
Contact Current Max
3A
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
230V
External Depth
86mm
Coil Frequency Max
60Hz
Coil Operating Frequency Min
50Hz
With electronic enabling circuits
Overview
The SIRIUS safety pilot guides you quickly to the right device
-- = not available
Design
The solid-state safety relays can be used in EMERGENCY-STOP
devices to EN 418 and in safety circuits to EN 60204-1 (11.98),
for example, for moving covers and protective doors.
Depending on the device type and the external circuit, the
maximum category that can be achieved is Category 4 of
EN 954-1 or SIL 3 according to IEC 61508.
Function
The electronics (based on the example of a 3TK28 41)
7
7
7
7
7
7
Type
3TK28 40
basic unit
3TK28 41
standard unit
3TK28 42
standard unit
tv
3TK28 45
multi-function
unit
Type
3TK28 40
basic unit
3TK28 41
standard unit
3TK28 42
standard unit
tv
3TK28 45
multi-function
unit
7/102
The internal circuit is configured with redundancy and
diversity. The processors monitor each other dynamically.
The output drivers are also redundant and diverse. They are
monitored by a cyclic self-test.
All sensor signals are dynamically tested. This enables faults
to be detected on the sensors, wires (cross-circuit) etc.
The field-effect transistor (FET) is switched by both
processors. The output driver must be activated
simultaneously by one of the two processors. Only then is the
voltage connected safely from power supply terminal A1 to
output terminals 14 + 24.
All solid-state switches (FET + output driver) are dynamically
monitored by the processors.
The required functionality (1-channel or 2-channel), monitored
start or autostart, EMERGENCY-STOP, protective door and
cascading is set by means of jumpers at the connection
terminals.
= available
3TK28 Safety Relays
Siemens LV 1 T · 2006
Connection
1-channel
Enabling circuit,
floating
Stop
category
0
--
--
--
1
2
Stop
category
1
--
--
--
--
1
2-channel
Enabling circuit,
solid-state
Stop
category
0
2
2
1
1
2
1)
Crossover
protection
Stop
category
1
--
--
1
1
--
Signal-
ing
circuit
Category acc. to EN 954-1
1 HL
1 HL
--
--
--
B
Autostart Moni-
1
2
tored
start
3
1) The outputs are only safe when an external contactor is used.
Installation
For snap-on mounting on 35 mm standard mounting rail
according to EN 50022. Screw fixing is also possible for the
devices by means of 2 additional 3RP19 03 push-in lugs.
4
--
Switching capacity Rated operational
AC-15
at
U=230 V
2 A
--
--
--
EMERGENCY-
STOP
DC-13
at
U=24 V
0.5 A
1.5 A
1.5 A
1.5 A
Protective
door
voltage
24 V
DC
230 V
AC
--
--
--
Solid-state
sensors
600 V
AC
--
--
--
--
--
Rated control supply
voltage
24 V
DC
Cascading
input
24 V DC
115 V
AC
--
--
--
--
--
1
1
1
230 V
AC
--
--
--
--
Safety mats
Control
inputs
24 V
DC
--
--
--
--
--

Related parts for 3UG4622-1AW30