3UG4622-1AW30 SIEMENS, 3UG4622-1AW30 Datasheet - Page 28

RELAY, MONITOR, 22.5MM

3UG4622-1AW30

Manufacturer Part Number
3UG4622-1AW30
Description
RELAY, MONITOR, 22.5MM
Manufacturer
SIEMENS
Series
3UG46r
Datasheet

Specifications of 3UG4622-1AW30

Contact Configuration
SPCO
Power Consumption
4VA
Supply Voltage Max
240VAC
Contact Current Max
3A
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
230V
External Depth
86mm
Coil Frequency Max
60Hz
Coil Operating Frequency Min
50Hz
SIMOCODE-DP 3UF5
motor protection and control devices
• Two speeds, Dahlander winding
• Two speeds, separate winding
• Valve
• Actuator
• Soft starter (3RW)
These control programs already include all the software
interlocks and logic operations required for operation of the
required motor functions.
It is also monitored whether the current checkback of the motor
feeder corresponds with the control command. If not,
SIMOCODE-DP opens the motor contactor and generates an
alarm indication.
The motor can be controlled by any equipment depending on
the application:
• From the process control system or the PC through
• From the control cabinet door through the operator panel
• From a local control point on the motor, whereby the
The standard control functions can also be adapted to each
customized variant of a motor feeder by means of freely-
parameterizable elements, such as timers, counters, logic
operations (AND, OR, NOR, etc.).
Integration
The SIMOCODE-DP modular system offers a wide range of
software packages for system-wide and time-saving
configuration and diagnostics:
• PC software Win-SIMOCODE-DP for start-up and service
• Object manager OM-SIMOCODE for "totally integrated" in
• Function block FB-SIMOCODE for "totally integrated" in PCS7
PC software Win-SIMOCODE-DP for start-up and service
Standard PC software Win-SIMOCODE-DP for start-up and
service. It offers a user-friendly and convenient user-interface
for:
• Parameterization
• Display and diagnostics
• Test functions
• Motor control
Win-SIMOCODE-DP is available in two versions:
• Win-SIMOCODE-DP/Smart
• Win-SIMOCODE-DP/Professional
OM-SIMOCODE object manager for "totally integrated" in
SIMATIC S7
SIMOCODE-DP can be integrated into SIMATIC S7 in two
different ways:
• Conventionally using GSD files
7/28
PROFIBUS DP
pushbuttons/switches are wired to the SIMOCODE-DP inputs
SIMATIC S7
for direct connection to SIMOCODE-DP through the system
interface on the device
for direct connection to SIMOCODE-DP over PROFIBUS or
directly through the system interface on the device
i.e. integration in SIMATIC S7 is identical to integration in any
other DP standard master system
SIMOCODE 3UF Motor Management and Control Devices
Siemens LV 1 T · 2006
Furthermore, special standard function blocks are stored in
SIMOCODE-DP:
• Automatic, time-discrete reactivation of motors following
• Different error signaling modules with and without
• The emergency start function
• The test function for the load feeder
• Using the OM-SIMOCODE-DP object manager
Both software packages must be installed on the PG/PC on
which the hardware configuration of SIMATIC S7 is performed.
This ensures that Win-SIMOCODE-DP/Professional can be
called up directly from HW-Config.
Parameter sets created with Win-SIMOCODE-DP/Professional
are loaded into the STEP 7 data storage by means of OM and
automatically transferred to SIMOCODE-DP during start-up.
Functions specific to SIMATIC S7, such as diagnostic and
hardware interrupts are supported, which means easier S7-wide
configuration as well as optimal performance in the transfer of
diagnostic data.
Function block FB-SIMOCODE for "totally integrated" in
PCS7
With PCS7-FB SIMOCODE-DP it is easy and convenient to
integrate SIMOCODE-DP into the SIMATIC PCS 7 process
control system. PCS7-FB SIMOCODE-DP contains the
diagnostic and driver blocks corresponding with the diagnostic
and driver concept of SIMATIC PCS 7 as well as the elements
(symbols and faceplate) required for operator control and
process monitoring. The application is integrated by graphic
interconnection using the CFC Editor. The technological and
signal processing functions of the PCS7-FB SIMOCODE-DP are
based on the SIMATIC PCS 7 standard libraries (driver blocks,
technological blocks) and are optimally tailored to SIMOCODE-
DP. Users who previously configured motor feeder circuits using
conventional technology by means of signal blocks and motor or
valve blocks, can now easily switch to PCS7-FB SIMOCODE-DP.
The PCS7-FB SIMOCODE-DP supplied on CD-ROM allows the
user to run the required engineering software on one
engineering station (single license) including the runtime
software for executing the AS blocks in an automation system
(single license).
- Failure of the three-phase supply must take place through a
- The supply voltage of SIMOCODE-DP must not be
mains failure
The prerequisites are as follows:
acknowledgement
These allow SIMOCODE-DP to trip as a result of external
events (e.g. overspeed monitor has tripped)
This resets the thermal memory of SIMOCODE-DP
immediately after overload tripping, i.e. immediate restarting
is possible (important, for example, for a fire-extinguisher
pump)
This can be activated by switching off the main switch Q1 (see
the section Schematics) and allows the control circuit to be
checked with the motor branch at zero current.
i.e. SIMOCODE-DP becomes an integral component of
STEP 7; the OM-SIMOCODE-DP object manager should, in
this case, always be combined with the start-up and service
software Win-SIMOCODE-DP/Professional
separate voltage relay
interrupted

Related parts for 3UG4622-1AW30