S3K2U1000-5 SOLA HEVI DUTY, S3K2U1000-5 Datasheet - Page 36

UPS - Uninterruptible Power Supplies 1000VA/750W 230V

S3K2U1000-5

Manufacturer Part Number
S3K2U1000-5
Description
UPS - Uninterruptible Power Supplies 1000VA/750W 230V
Manufacturer
SOLA HEVI DUTY
Datasheet

Specifications of S3K2U1000-5

Power Rating
1000 VA
Output Voltage Rating
230 V
Number Of Outlets
8
Interface Port
USB / SNMP
Runtime (full Load)
5 min
Runtime (half Load)
12 min
Topology
Line Interactive
Tower / Rackmount
Tower / Rackmount
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
UPS will not start
UPS starts on battery, but will not
switch to AC
UPS shuts down
All Battery Level Indicators
flashing
Battery Indicator illuminated
amber; long beep every minute
Over Temp Indicator flashing
Fault Indicator lit but UPS is On
If the UPS fails to operate properly, turn Off the unit and repeat the steps in 5.0 - Installation. If the
problem persists, refer to Table 3:
Table 3
Problem
Troubleshooting chart
Short circuit
Battery disconnected or is
completely discharged
UPS not plugged in
Circuit protector tripped
Input voltage below threshold
AC overvoltage
Load exceeded UPS capacity
(110%), All Load Level Indicators
are illuminated; continuous beep
Over temperature shutdown, Over
Temp Indicator lit; continuous
beep
MultiLink shutdown
Internal UPS fault, Fault Indicator
Lit; continuous beep
UPS shutdown due to a command
from the communications port(s),
Load Level 0-25% Indicator
illuminated
UPS is unable to perform manual
or remote battery test; beep every
half second for five seconds
UPS failed battery test
Batteries weak
Batteries need to be replaced
Over temperature warning; beep
every half second
Fault warning; beep every half
second
Cause
30
Check the circuit protector on the rear of the UPS.
If it is tripped, reset it and restart the UPS. For
further help, contact your local distributor, Sola/
Hevi-Duty representative, or Sola/Hevi-Duty
Technical Services.
Check for proper connection of battery or
batteries.
Plug in the power cord securely.
Reset the circuit protector and restart the UPS.
Wait until the voltage rises to an appropriate level
or have the mains power checked by a qualified
electrician.
Wait until voltage lowers to an appropriate level
or have the mains power checked by a qualified
electrician.
Check load level display and remove non-
essential loads. Recalculate the load and reduce
number of loads connected to UPS - the total
wattage of your equipment must not exceed the
capacity of the UPS.
Make sure that the UPS is operating in 0°C to
40°C (32°F to 104°F) and that it has adequate
ventilation.
Consult the MultiLink user manual or contact your
LAN administrator.
Contact your local distributor, Sola/Hevi-Duty
representative, or Sola/Hevi-Duty Technical
Services.
Your UPS has received a signal or command
from the attached computer. If this was
inadvertent, ensure the communication cable
used is correct for your system. For assistance,
contact your local distributor, Sola/Hevi-Duty
representative, or Sola/Hevi-Duty Technical
Services.
Check battery connections,
completely power down and restart UPS.
NOTE: If the battery circuit opens while the UPS
is running, it will be detected when the next
battery test is performed.
Initiate battery test again.
Recharge batteries.
Replace batteries.
Make sure that the UPS is operating in 0°C to
40°C (32°F to 104°F) and that it has adequate
ventilation.
Reset UPS.
Solution
Troubleshooting