Connecting the Special Cable
Mounting to a Control
Panel
30
1,2,3...
Control panel
Adjust the cable length,
place the rubber cable packing
inside the housing, and then tighten
the cap to secure the cable.
A UL-standard cable connection example is given below.
1. When using a UL-standard cable, it is necessary to cut a hole in the control
2. Feed the UL-standard cable through the hole, then secure the cable clamp
panel to secure the cable clamp.
to the control panel from the inside using the lock nut. When using the
NSH5-232UL-3M/10M, always connect the relay cable, which is equipped
with an RS-232C connector, after feeding the UL-standard cable through
the hole in the wall of the control panel. Tighten the lock nut to a force of
2.0 to 3.0 N·m.
Cut a cable clamp mounting hole in
the control panel, using the cable
diameter as a guide, then feed the
cable through the hole.
23±0.2 mm
Insert the cable clamp housing into the
mounting hole in the control panel and
secure it in place with the lock nut from the inside.
Tighten the lock nut to a torque of 4.0 to 5.0 N·m.
Cap
Cable Clamp Mounting Hole Dimension
Cable
packing
Relay cable (included)
*Connect the relay cable after first feeding
the UL-standard cable through the control panel wall.
Housing
Lock nut
Section 2-3