DRT2-MD32B Omron, DRT2-MD32B Datasheet - Page 441

no-image

DRT2-MD32B

Manufacturer Part Number
DRT2-MD32B
Description
16In,16Out Horiz MIL Conn NPN
Manufacturer
Omron
Datasheet

Specifications of DRT2-MD32B

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Temperature Input Terminals
420
3. Click the Comparator Tab and set each of the alarm values. The example
4. To set the hysteresis value, input the desired value in the Hysteresis field.
here shows the setting for Alarm Trip Point High (HH limit set value).
Note When setting the hysteresis value, adjust for each input’s decimal
Note The hysteresis value set for the comparator function is also used by
point position or the 1/100 display mode if the 1/100 display mode is
being used. Always correct the hysteresis value after changing the
display mode setting or replacing the sensor with a sensor that has
a different decimal point position.
Example hysteresis value settings for 10 ° C:
a) R thermocouple (normal display) setting: 0010 decimal
b) T thermocouple (normal display) setting: 0100 decimal
c) Setting for any input with 1/100 display: 1000 decimal
the top/valley hold function.
Section 7-6

Related parts for DRT2-MD32B