H3CR-F8 AC/DC24 Omron, H3CR-F8 AC/DC24 Datasheet - Page 4

TIMER REPEAT CYCLE

H3CR-F8 AC/DC24

Manufacturer Part Number
H3CR-F8 AC/DC24
Description
TIMER REPEAT CYCLE
Manufacturer
Omron
Series
H3CR-Fr
Datasheet

Specifications of H3CR-F8 AC/DC24

Rohs Compliant
YES
Relay Type
Integrated
Function
Repeat Cycle
Circuit
DPDT (2 Form C)
Delay Time
0.05 Sec ~ 30 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
24VAC/DC
Mounting Type
Socket
Termination Style
8 Pin Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage
Contact Configuration
DPDT
Timing Adjustment
Knob
Relay Mounting
Panel
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H3CR-F8-AC/DC24
H3CR-F8-AC/DC24
H3CRF8ACDC24
Z2382
■ Life-test Curve
Connections
■ Block Diagrams
■ I/O Functions
■ Terminal Arrangement
Inputs
Outputs
10,000
5,000
1,000
500
100
AC (DC) input
250 VAC (cosφ = 0.4)
30 VDC L/R = 7 ms
Control output
Load current (A)
H3CR-F8
H3CR-F8
NH3CR-F8-300
H3CR-F8N-300
http://www.ia.omron.com/
250 VAC/30 VDC
(cosφ = 1)
Power supply
circuit
Power supply
---
Outputs are turned ON/OFF according to the time set by the ON- and OFF-time setting knob.
ON indicator
Indicator
circuit
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)
OFF indicator
ROM
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In
both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
One-chip microcomputer
RAM
Zero setting
detection
circuit
Note: Leave terminals 5, 6, and 7 open.
H3CR-F
H3CR-FN
H3CR-F-300
H3CR-FN-300
Clock
Do not use them as relay terminals.
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
Power supply
Time range/unit
selectors
(+)(~)
Output
circuit
H3CR-F
4