5-2-4 Copying Memory Table Entries
212
Memory Tables and Graphs
The following describes the procedure to change displayed numerals or charac-
ter strings by copying the contents of a memory table entry.
Numerals and character strings can be changed also by changing the contents of
the allocated words. Refer to Changing Displayed Numerals or Character strings
(pages 207, 209) explained before.
To change the numerals or character strings displayed on the NT30/30C, copy
the data between the numeral or character string memory table entries by using
the copy memory table entry setting of the PT Status Control Area.
Write a memory table entry number etc. to the copy memory table entry setting
area in the PT Status Control Area in the PC memory. Data will be copied be-
tween the memory table entries in the NT30/30C and the displayed value will
change accordingly.
This procedure is convenient to switch predetermined values or character
strings according to the situation. By preparing several units of contents, various
contents can be displayed by switching them to suit the situation.
Copy Memory Table Entry Setting in the PT Status Control Area
A
Copy type:
Copy source and destination memory table entry numbers:
NT30/30C
Word
n+1
n+2
0: Copy between the character string memory table entries
1: Copy between the numeral memory table entries
1:
Character string memory table entries: 000 to 999 (Numbers 256 to
999 are read-only memory table entries. They cannot be used as
copy destinations. In addition, depending on the setting made in the
system memory settings of the NT-series Support Tool, it may not be
possible to use numbers 256 through 999.
Numeral memory entries: 000 to 999 (Depending on the setting
made in System under PT Configuration (System Memory with the
DOS version) of the NT-series Support Tool, it may not be possible to
use numbers 512 through 999).
15 14 13 12 11 10 9
2 to F (nothing happens)
Copy type
0
Memory table
copy source
A
A
Copy destination
(for display)
Destination memory table entry # (3-digit BCD)
Source memory table entry # (3-digit BCD)
8
7
6
5
4
PT status control area
Screen switch setting
PT status control setting
3
PC
Copy memory table
setting
2
1
0 Bit
Copy memory
table entry
setting
Section
Copy source number
Copy destination
number
5-2