S701E15N3S EATON CUTLER HAMMER, S701E15N3S Datasheet - Page 5

Motor Starter

S701E15N3S

Manufacturer Part Number
S701E15N3S
Description
Motor Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of S701E15N3S

No. Of Phases
Three
Power Rating
10hp
Current Rating
15A
Peak Reflow Compatible (260 C)
No
Output Current
15A
Supply Voltage Max
415VAC
Control Voltage Max
480V
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Figure 12. Adjust Time and Torque
How to Adjust Time and Torque, Figure 12
Control of the motor torque is achieved by acting on the motor
voltage.The motor speed depends on the torque produced by
the motor and the load on the motor shaft. A motor with little or
no load will reach full speed before the voltage has reached its
maximum value.
NOTE: The soft start controller will read time and torque set-
Rating Index
Table 8. Rating Index
Ramp-Up Time and Initial Torque
Table 9. Ramp-Up Time and Initial Torque
(Standard Load)
Effective 01/02
S701_15N3S
15A: AC-52a: 4-13 : 100 – 3000
15A: AC-53a: 8-3 : 100 – 3000
15A: AC-58a: 6-6 : 100 – 3000
Position
8,2
0
0
0
S701E25N3S
92EQ10005A0001A
tings in the OFF state. Repeated starts may trip the
motor protection relay. DO NOT set the rotary
switches in between positions. This corrupts the time
and torque adjustment. Use screwdriver 2 mm x
0.5 mm.
Setting/Adjustment
Set the Ramp-Up switch to maximum.
Set the Ramp-Down switch to minimum.
Set the Initial Torque switch to minimum.
Apply control signal for a few seconds. If the load does not
rotate immediately, increment the Initial Torque and try
again. Repeat until the load starts to rotate immediately on
startup.
Adjust Ramp-Up time to the estimated start time (the
scale is in seconds) and start the motor.
Decrease the Ramp-Up time until mechanical surge is
observed during start.
Increase the time one step to eliminate the surge.
1/L1
2 /T1
3 /L2
4/T2
5/L3
6/T3
J
U
U
U
A1
t
t
t
t
Ramp up
Ramp down
Initial torque
Kick start
A2
S701_25N3S
25A: AC-52a: 4-13 : 100 – 3000
25A: AC-53a: 8-3 : 100 – 3000
25A: AC-58a: 6-6 : 100 – 3000
4
6
2
0
0
2
6
11
4
5,6
5,6
8,2
8,2
3,9
3,9
4
6
2 0
2,7
2,7
12
0
0
0
0,8
0,8
1,8
2
1,8
6
1,2
1,2
4
Torque Adjustment, 0 - 85%
Ramp-Down, 0.5 - 10 Sec.
Ramp-Up, 0.5 - 10 Sec.
200ms kick start with
Adj. Torque, 0 - 85%
Kick Start/Break Loose
If it is not possible to reach a time sufficient for the application,
it may be necessary to kick start the load.
Table 10. Kick Start/Break Loose (High Inertia Loads)
Ramp-Down Time
Follow Table 9 to set Ramp-Up and Initial Torque.
Table 11. Ramp-Down Time, e.g. Pump Loads
Position
Position
8,2
8,2
0
0
0
0
0
100%
Motor Voltage
0
Setting/Adjustment
Set the Ramp-Up switch to maximum.
Set the Ramp-Down switch to minimum.
Set the Initial Torque switch to minimum kick
start torque.
Apply control signal for a few seconds. If the load stops
right after the 200ms “kick”, increment the Initial Torque
and try again. Repeat until the load continues to rotate
after the “kick”.
Adjust Ramp-Up time to the desired start time (the scale is
in seconds) and start the motor.
Setting/Adjustment
Set the Ramp-Down switch to maximum.
Switch off the control voltage and observe any mechanical
surges on the load. If there are none, decrement Ramp-
Down switch and try again. Repeat until mechanical surge
on the load is observed.
Increase the time one step to eliminate the surge.
Pub 49440
Time
5