Specifications of CV500II101

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Operating Errors
5-2
5-3
Cannot connect
Comm error
Comm err wait’g
Response overflo
# of data error
Add range exceed
Address too high
Can’t chg; active
File not found
Instr not found
Memory error
Mode error
No access right
Error message
Error Messages
Operating Errors
Error message
The source node did not have the designated
number of data when the data was transferred from
the memory card to PC or from the PC to memory
card.
The memory card does not have enough space.
The user attempted to read in an area exceeding the
highest address of the user program.
The designated word and data area exceeds the
possible range.
No action can be changed because the designated
step is active.
The designated file does not exist in the memory
card.
The designated instruction does not exist in the user
memory.
A parity or check sum error occurred in PC memory.
The user program is not correct.
An error occurred in the memory card.
An access error occurred while the user was
accessing the memory card.
A checksum error occurred for the data in the
memory card.
An operation was attempted in the wrong PC mode
(RUN, MONITOR, DEBUG, PROGRAM).
No data can be changed because data is being
written by another Programming Device.
Error History Read
It is possible to read the data recorded in the error history area by pressing the
Clear Key, Function–Monitor Keys, and 1 Key.
Another Programming Device was
already connected or a Programming
Device with a higher priority was
connected.
There is a communications error
between the PC and Programming
Console.
Time ran out before a response has
returned for a command.
A communications error has occurred.
Probable cause
Probable cause
Check the user program.
Check the number of send words.
Check the file designation.
Use another memory card.
Delete unnecessary files.
Check the input address and input the
address correctly.
Check the operating condition of the
PC.
Check the file name.
Check the user program.
Correct the data in memory.
Check and correct the program with the
CVSS/SSS or GPC and transfer the
program to the PC again.
Mount the memory card correctly.
Check and correct the data in the
memory card.
Set the PC to the correct mode.
Write the data after the other
Programming Device finishes writing
the data.
Do not connect more than one
Programming Device to the CPU Unit
or I/O Interface Unit.
Check the destination Unit.
Check the cable connections.
Check the communications path
between the Programming Console
and PC.
Possible correction
Possible correction