E1IM10AACL10 TELE, E1IM10AACL10 Datasheet - Page 2

no-image

E1IM10AACL10

Manufacturer Part Number
E1IM10AACL10
Description
CURRENT MONITORING 1-PHASE
Manufacturer
TELE
Series
ENYAr
Datasheet

Specifications of E1IM10AACL10

Contact Configuration
SPCO
Power Consumption
5VA
Supply Voltage Max
230VAC
Contact Current Max
5A
Relay Mounting
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Contact Current Ac Max
5A
Contact
RoHS Compliant
Functions
Overcurrent monitoring (OVER, OVER+Latch)
When the supply voltage U is applied, the output relay R switches into
on-position, if the measured current is below the Max-value.
When the measured current exceeds the Max-value, the output relay R
switches into off-position after the interval of the tripping delay (Delay)
has expired.
OVER:
The output relay R switches into on-position again, if the current falls
below the Min-value.
OVER+Latch:
The output relay R switches only into on-position again by interrupting
and re-applying of the supply voltage, provided that the measured
current is below the Max-value.
Window function (WIN, WIN+Latch)
When the supply voltage U is applied, the output relay R switches into
on-position, if the measured current is within the adjusted window.
When the measured current leaves the window between Min and Max,
the output relay R switches into off-position after the interval of the
tripping delay (Delay) has expired.
WIN:
The output relay R switches into on-position again, if the current re-enter
the adjusted window.
WIN+Latch:
The output relay R switches only into on-position again by interrupting
and re-applying of the supply voltage, provided that the measured
current is within the threshold values.
Latch
Latch
latch activated
latch activated
www.tele-online.com
Untercurrent monitoring (UNDER, UNDER+Latch)
When the supply voltage U is applied, the output relay R switches into
on-position, if the measured current is beyond the Min-value.
When the measured current falls below the Min-value, the output relay
R switches into off-position after the interval of the tripping delay (Delay)
has expired.
UNDER:
The output relay R switches into on-position again, if the current
exceeds the Max-value.
UNDER+Latch:
The output relay R switches only into on-position again by interrupting
and re-applying of the supply voltage, provided that the measured
current is beyond the Min-value.
Latch
E1IM10AACL10
latch activated