D6DI TELE, D6DI Datasheet

ASYMMETRIC FLASHER, 1 CO

D6DI

Manufacturer Part Number
D6DI
Description
ASYMMETRIC FLASHER, 1 CO
Manufacturer
TELE
Datasheet

Specifications of D6DI

Contact Configuration
SPCO
Nom Input Voltage
240VAC
Delay Time Range
50ms To 10days
Adjustment Type
Knob
Relay Mounting
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Coil Voltage Vac Nom
250V
Contact Current Ac
RoHS Compliant
Timers - DELTA series
1. Functions
2. Time ranges
Time range
3. Indicators
Green LED ON:
Green LED fast flashing:
Green LED slow flashing:
Yellow LED ON/OFF:
4. Mechanical design
Self-extinguishing plastic housing,IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position:
Shockproof terminal connection according to VBG 4
(PZ1 required), IP rating IP20
Tightening torque:
Terminal capacity:
5. Input circuit
Supply voltage:
Tolerance:
Rated frequency:
Rated consumption:
Duration of operation:
Reset time:
Residual ripple for DC:
Drop-out voltage:
Asymmetric fl asher
8 time ranges
1 change-over contact
Width 22.5 mm
Industrial design
Technical data
Release 12/05
Ip
Ii
1s
10s
1min
10min
1h
10h
1d
10d
1 x 0.5 to 2.5mm
1 x 4mm
2 x 0.5 to 1.5mm
2 x 2.5mm
24V DC
24V AC
110 to 240V AC
24V DC
24V AC
110 to 240V AC
24V AC/DC
110V AC
230V AC
2
without multicore cable end
2
flexible without multicore cable end
2
2
any
max. 1Nm
with/without multicore cable end
with/without multicore cable end
Asymmetric fl asher pause fi rst
Asymmetric fl asher pulse fi rst
(A1-B1 bridged)
Adjustment range
50ms
500ms
3s
30s
3min
30min
72min
12h
terminals A1(+)-A2
voltage selector engaged
terminals A1-A2
voltage selector engaged
terminals A1-A2
voltage selector not engaged
±10%
-15% to+10%
-15% to+10%
48 to 63Hz
1.5VA (1W)
2VA (1W)
8VA (1.3W)
100%
250ms
10%
>30% of the supply voltage
indication of supply voltage
indication of time period t2
indication of time period t1
indication of relay output
1s
10s
1min
10min
1h
10h
1d
10d
6. Output circuit
1 potential free change-over contact
Switching capacity (distance < 5mm):
Switching capacity (distance > 5mm):
Fusing:
Mechanical life:
Electrical life:
Switching frequency:
Insulation voltage:
Surge voltage:
7. Accuracy
Base accuracy:
Adjustment accuracy:
Repetition accuracy:
Voltage influence:
Temperature influence:
8. Ambient conditions
Ambient temperature:
Storage temperature:
Transport temperature:
Relative humidity:
Pollution degree:
1250VA (5A/250V AC)
2000VA (8A/250V AC)
8A flink
20 x 10
2 x 10
at 1000VA resistive load
max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(according to IEC 947-5-1)
250V AC (according to IEC 664-1)
4kV, overvoltage category III
(according to IEC 664-1)
±1% of maximum scale value
5% of maximum scale value
<0.5% or ±5ms
0.01%/°C
-25 to+55°C (according to IEC 68-1)
-25 to+40°C (according to UL 508)
-25 to+70°C
-25 to+70°C
15% to 85%
(according to IEC 721-3-3 class 3K3)
3 (according to IEC 664-1)
5
6
operations
operations
D6DI
3.02-10

Related parts for D6DI

D6DI Summary of contents

Page 1

... Duration of operation: 100% Reset time: 250ms Residual ripple for DC: 10% Drop-out voltage: >30% of the supply voltage Release 12/05 D6DI 6. Output circuit 1 potential free change-over contact Switching capacity (distance < 5mm): 1250VA (5A/250V AC) Switching capacity (distance > 5mm): 2000VA (8A/250V AC) Fusing: 8A flink 6 ...

Page 2

... D6DI Functions Asymmetric flasher pause first (lp) When the supply voltage U is applied, the set interval t1 begins (green LED flashing slowly). After the interval t1 has expired, the output relay R switches into on-position (yellow LED illuminated) and the set inter- val t2 begins (green LED flashing fast). After the interval t2 has expired, the output relay switches into off-position (yellow LED not illuminated) ...

Related keywords