D6DS TELE, D6DS Datasheet
D6DS
Manufacturer Part Number
D6DS
Description
STAR-DELTA TIMER, 2 NO
Manufacturer
TELE
Datasheet
1.D6DS.pdf
(2 pages)
Specifications of D6DS
Contact Configuration
DPNO
Nom Input Voltage
240VAC
Delay Time Range
500ms To 3min
Adjustment Type
Knob
Relay Mounting
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Coil Voltage Vac Nom
250V
Contact Current Ac
RoHS Compliant
Timers – DELTA series
Industrial design
Width 22.5mm
Star-Delta start-up
2 normally opened contacts
Technical data
1. Functions
S
2. Time ranges
Start-up time
Transit time
3. Indicators
Green LED ON:
Green LED flashes:
Yellow LED ON/OFF:
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position:
Shockproof terminal connection according to VBG 4
(PZ1 required), IP rating IP20
Initial torque:
Terminal capacity:
5. Input circuit
Supply voltage:
Tolerance:
Rated frequency:
Rated consumption:
Duration of operation:
Reset time:
Residual ripple for DC:
Drop-out voltage:
Release 11/01
Time range
10s
30s
1min
3min
Time range (fixed)
40ms
60ms
80ms
100ms
Star-Delta start-up
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
24V DC
24V AC
110 to 240V AC
24V DC
24V AC
110 to 240V AC
24V AC/DC
110V AC
230V AC
Adjustment range
500ms
1500ms
3s
9s
indication of supply voltage
delta-contactor in on-position
(terminals 17-28)
indication of star-time
indication of star-contactor
(terminals 17-18)
any
max. 1Nm
terminals A1(+)-A2
voltage selector engaged
terminals A1-A2
voltage selector engaged
terminals A1-A2
voltage selector not engaged
±10%
-15% to +10%
-15% to +10%
48 to 63Hz
1.5VA (1W)
2VA (1W)
8VA (1.3W)
100%
100ms
10%
>30% of the supply voltage
10s
30s
1min
3min
6. Output circuit
2 potential free normally opened contacts
Switching capacity (distance < 5mm): 1250VA (5A / 250V AC)
Switching capacity (distance > 5mm): 2000VA (8A / 250V AC)
Fusing:
Mechanical life:
Electrical life:
Switching frequency:
Insulation voltage:
Surge voltage:
7. Accuracy
Base accuracy:
Adjustment accuracy:
Repetition accuracy:
Voltage influence:
Temperature influence:
8. Ambient conditions
Ambient temperature:
Storage temperature:
Transport temperature:
Relative humidity:
Pollution degree:
9. Dimensions
8A fast acting
20 x 10
2 x 10
at 1000VA resistive load
max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(according to IEC 947-5-1)
250V AC (according to IEC 664-1)
4kV, overvoltage category III
(according to IEC 664-1)
D6DS
±1% (of maximum scale value)
≤5% (of maximum scale value)
<0.5% or ±5ms
-
≤0.01% / °C
-25 to +55°C (according to IEC 68-1)
-25 to +40°C (according to UL 508)
-25 to +70°C
-25 to +70°C
15% to 85%
(according to IEC 721-3-3 class 3K3)
3 (according to IEC 664-1)
5
6
operations
operations
1.02 – 7
Related parts for D6DS
D6DS Summary of contents
Page 1
... Reset time: 100ms Residual ripple for DC: 10% Drop-out voltage: >30% of the supply voltage Release 11/01 D6DS 6. Output circuit 2 potential free normally opened contacts Switching capacity (distance < 5mm): 1250VA (5A / 250V AC) Switching capacity (distance > 5mm): 2000VA (8A / 250V AC) Fusing: 8A fast acting Mechanical life: ...
Page 2
... D6DS Functions Star-Delta start-up (S) When the supply voltage U is applied, the contact for the star- contactor switches into on-position (yellow LED illuminated) and the set star-time t1 begins (green LED flashes). After the interval t1 has expired (green LED illuminated) the contact switches into off-position (yellow LED not illuminated) and the set transit-time t2 begins ...