3UG4622-1AW30 SIEMENS, 3UG4622-1AW30 Datasheet - Page 12

RELAY, MONITOR, 22.5MM

3UG4622-1AW30

Manufacturer Part Number
3UG4622-1AW30
Description
RELAY, MONITOR, 22.5MM
Manufacturer
SIEMENS
Series
3UG46r
Datasheet

Specifications of 3UG4622-1AW30

Contact Configuration
SPCO
Power Consumption
4VA
Supply Voltage Max
240VAC
Contact Current Max
3A
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
230V
External Depth
86mm
Coil Frequency Max
60Hz
Coil Operating Frequency Min
50Hz
SIMOCODE pro 3UF7
motor management and control devices
Monitoring additional process variables over analog inputs
(0/4 ... 20 mA)
• The analog module enables SIMOCODE pro to measure
• SIMOCODE pro supports two-step monitoring of the corre-
Phase sequence detection
• By detecting the phase sequence, SIMOCODE pro is able to
Monitoring of operating hours, downtime and number of starts
• In order to prevent plant downtime caused by motor failure
• To avoid excessive thermal loads and early wear of the motor,
Flexible motor control implemented with software
Many typical motor control functions have been predefined in
SIMOCODE pro and are available for use:
• Direct-on-line and reversing starters
• Wye-delta starters (also with direction reversal)
• Two speeds, motors with separate windings (pole-changing
• Two speeds, motors with separate Dahlander windings
• Slide control
• Solenoid valve actuation
• Actuation of a circuit-breaker (MCCB)
• Actuation of a 3RW soft starter also with direction reversal
These control programs already include all the software
interlocks and logic operations required for operation of the
required motor functions.
It is also monitored whether the current checkback of the motor
feeder corresponds with the control command. If not,
SIMOCODE pro opens the motor contactor and generates an
alarm indication.
Depending on the application, motor control can be switched
over or carried out simultaneously from several control stations,
e.g.:
• From the I&C system through PROFIBUS DP
• From a PC/PG through PROFIBUS DP
• From the control cabinet door through the operator panel
• From a PC/PG on the system interface through
• From a local control station on the motor. In this case, the
7/12
additional process variables and monitor them. A pump can,
for example, be protected against dry running in this manner
with level monitoring or the degree of pollution of a filter can
be measured using a differential pressure transducer. When a
specified level is undershot, the pump can be deactivated
and when a specified differential pressure is overshot, the filter
can be cleaned.
sponding process variable for freely selectable upper and
lower current limit values. The response of SIMOCODE pro
can be freely configured and delayed if it reaches an alarm or
tripping threshold.
make a statement about the direction of rotation of a motor. If
the direction is incorrect, this can be reported or it can result
in immediate shutdown of the affected motor.
due to excessive motor operating times (wear) or excessive
motor downtimes, SIMOCODE pro can monitor the operating
hours and downtime of a motor. When an adjustable limit value
is violated, a message or alarm can be generated which can
indicate that the corresponding motor must be serviced or
replaced. After the motor has been replaced, the operating
hours and downtimes can be reset, for example.
it is possible to limit the number of motor startups for a
specifiable period. Alarms can indicate that only a small
number of possible starts remain.
switch); also with direction reversal
(also with direction reversal)
SIMOCODE pro
buttons, switches and indicator lights are connected to the
inputs and outputs of SIMOCODE pro.
SIMOCODE 3UF Motor Management and Control Devices
Siemens LV 1 T · 2006
1)2)
1)
1)
3)
1)
1)
1)
1)
Regardless of whether a control command is sent to SIMOCODE
pro via PROFIBUS DP using the operator module or via the
buttons connected to the binary SIMOCODE pro inputs,
SIMOCODE pro can execute these control commands
simultaneously or in accordance with the enabled commands
defined during configuration.
These predefined control functions can also be flexibly adapted
to each customized configuration of a motor feeder by means of
freely configurable logic modules (truth tables, counters, timers,
edge evaluation etc.).
In addition, special standard functions are stored in
SIMOCODE pro which can also be used to extend the protection
and control functions, e.g.:
• Power failure monitoring
• Fault signaling modules for external faults with or without
• Emergency start function and reset of the thermal memory of
• Test function for the load feeder circuit when the main control
Detailed operational, service and diagnostics data
SIMOCODE pro provides a variety of operating, service and
diagnostic data, such as:
Operating data
• The switching state of the motor (On, Off, clockwise, counter-
• Current in phase 1, 2, 3 and maximum current in % of the set
• Voltage in phases 1, 2, 3 in V
• Active power in W
• Apparent power in VA
• Power factor in %
• Phase unbalance in %
• Phase sequence
• Temperature in sensor circuits 1, 2, 3 and maximum
• Current values of the analog signals
• Time until tripping in sec.
• Temperature rise for motor model in %
• Remaining cooling time of the motor in sec. etc.
Service data
• Motor operating hours (can be reset)
• Motor stop times (can be reset)
• Number of motor starts (can be reset)
• Number of remaining permissible motor starts
• Number of overload trips (can be reset)
• Internal comments, stored in the device for each feeder,
1) Using basic unit 2.
2) An additional analog module is required.
3) Using basic unit 2 with current/voltage measuring module.
4) An additional temperature module is required.
restart of motors following a network failure e.g. with the help
of a separate voltage relay (voltage controller).
manual or automatic acknowledgement for generating internal
messages or for tripping SIMOCODE pro in response to freely
definable events (e.g. overspeed monitor has been
activated). Designations/names can also be assigned to the
external faults which are stored in the device and which are
therefore also available to the I&C system.
SIMOCODE pro after tripping, i.e. immediate restart is
possible (important, for example, for pumps used to
extinguish fires).
switch is open to test the control circuit while the main circuit
is de-energized.
clockwise, fast, slow) is derived from the current flow in the
main circuit, so checkbacks are not required through auxiliary
contacts from circuit-breakers and contactors
current
temperature in °C
e.g. notes for maintenance events etc.
3)
3)
1)4)
3)
3)
1)
for automatic, time-staggered
3)
1)2)