3UG4622-1AW30 SIEMENS, 3UG4622-1AW30 Datasheet - Page 11

RELAY, MONITOR, 22.5MM

3UG4622-1AW30

Manufacturer Part Number
3UG4622-1AW30
Description
RELAY, MONITOR, 22.5MM
Manufacturer
SIEMENS
Series
3UG46r
Datasheet

Specifications of 3UG4622-1AW30

Contact Configuration
SPCO
Power Consumption
4VA
Supply Voltage Max
240VAC
Contact Current Max
3A
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
230V
External Depth
86mm
Coil Frequency Max
60Hz
Coil Operating Frequency Min
50Hz
Function
Multifunctional, solid-state full motor protection
Current-dependent electronic overload protection with
adjustable tripping characteristics (Classes 5, 10, 15, 20, 25, 30,
35 and 40)
• SIMOCODE pro protects three-phase or AC motors according
Phase failure/unbalance protection
• The level of the phase unbalance can be monitored and trans-
Stall protection
• If the motor current rises above an adjustable blocking
Thermistor motor protection
• This protection function is based on direct temperature
Ground-fault monitoring (internally) with a current measuring
module or current/voltage measuring module
• SIMOCODE pro acquires and monitors all three phase
Ground-fault monitoring (external) with summation current
transformer
• External ground-fault monitoring is normally implemented for
to IEC 60947-4-1 requirements. The trip class can be adjusted
in eight steps from Class 5 to Class 40. In this way, the break
time can be adapted very accurately to the load torque which
allows the motor to be utilized more effectively. In addition, the
time until the overload tripping operation is performed is
calculated and can be made available to the I&C system. After
an overload tripping operation, the remaining cooling time can
be displayed (characteristic curves for 2-pole and 3-pole
loading in SIMOCODE pro System Manual).
mitted to the I&C system. If a specified limit value is violated,
a defined and delayable response can be initiated. If the
phase unbalance is larger than 50 %, the tripping time is also
automatically reduced according to the overload characteris-
tic since the heat generation of the motors increases in unbal-
anced conditions.
threshold (current threshold), a defined and delayable
response can be configured for SIMOCODE pro. In this case,
for example, the motor can be shut down independent of the
overload protection. The blocking protection is only enabled
after the configured class time has elapsed and avoids
unnecessarily high thermal and mechanical loads as well as
wear of the motor.
measurements by means of temperature sensors in the stator
windings or in the enclosure of the motor. These protective
functions should be used, in particular, in motors with high
operating frequencies, heavy-duty starting, intermittent and/or
braking operation, but also in the case of speeds lower than
the rated speed. SIMOCODE pro supports connection and
evaluation of several PTC sensors connected in series on the
basic unit. In addition, the sensor measuring circuit can be
monitored for short-circuits and wire breakages. If the
temperature of the motor increases beyond a defined limit or
if there is a fault in the sensor measuring circuit, a defined
response can be configured.
currents. With vector addition of the phase currents, the motor
feeder can be monitored for possible fault currents or ground
faults with the help of internal calculations. Internal earth fault
monitoring is only available for motors with three-phase
connections in directly grounded networks or in networks
grounded with low impedance. The response of
SIMOCODE pro when a ground fault is detected can be
parameterized and delayed as required.
networks that are grounded with high impedance. Using an
additional summation current transformer (3UL2 20.-.A), even
extremely low ground-fault currents can be measured. The
response of SIMOCODE pro when a ground fault is detected
can be parameterized and delayed as required. Fault current
measurement is performed for each summation current
transformer for the following fault currents: 0.3/0.5/1 A
1)2)
SIMOCODE 3UF Motor Management and Control Devices
Monitoring of adjustable limit values for the motor current
• Current limit value monitoring is used for process monitoring
Voltage monitoring
• By measuring the voltage directly at the circuit-breaker or at
• SIMOCODE pro supports two-stage undervoltage monitoring
Monitoring the active power
• The active power characteristic of a motor provides an
• SIMOCODE pro supports two-step monitoring of the active
Monitoring the power factor
• Especially in the low-end performance range of a motor, the
• SIMOCODE pro supports two-stage monitoring of power
Temperature monitoring
• The temperature can be monitored, for example, in the motor
• SIMOCODE pro supports two-stage monitoring of overheating
1) Using basic unit 2.
2) An additional ground-fault module with a 3UL22 summation current
3) Using basic unit 2 with current/voltage measuring module.
4) An additional temperature module is required.
independent of overload protection. Violation of a current limit
value below the overload threshold can be an indication for a
dirty filter in a pump or for an increasingly sluggish motor
bearing, for example. Violation of the lower current limit value
can be a first indication of a worn drive belt. SIMOCODE pro
supports two-step monitoring of the motor current for freely
selectable upper and lower current limit values. The response
of SIMOCODE pro can be freely configured and delayed if it
reaches an alarm or tripping threshold.
the fuses in the main circuit, even when the motor is
deactivated, SIMOCODE pro can also obtain information
about the reclosing capability of the feeder and signal it if
required.
for freely selectable limit values. The response of
SIMOCODE pro can be freely configured and delayed if it
reaches an alarm or tripping threshold.
accurate statement of the actual loading over the complete
range. Excessive loading will cause increased wear in the
motor and can result in early failure. Insufficient active power
can be an indication of, for example, motor idling.
power for freely selectable upper and lower current limit
values. The response of SIMOCODE pro can be freely
configured and delayed if it reaches an alarm or tripping
threshold.
power factor varies more than the motor current or active
power. Monitoring of the power factor is therefore particularly
useful for distinguishing between motor idling and fault events
such as a tear in a drive belt or a crack in a drive shaft.
factor undershoot for freely selectable limit values. The
response of SIMOCODE pro can be freely configured and
delayed if it reaches an alarm or tripping threshold.
windings or at the bearings through up to three resistance
sensors connected to the temperature module.
for freely selectable limit values. The response of
SIMOCODE pro can be freely configured and delayed if it
reaches an alarm or tripping threshold. Temperature
monitoring is always performed with reference to the highest
temperature of all sensor measuring circuits used.
transformer is required.
motor management and control devices
3)
1)4)
3)
3)
Siemens LV 1 T · 2006
SIMOCODE pro 3UF7
7/11