S201MB40 ABB, S201MB40 Datasheet - Page 22

no-image

S201MB40

Manufacturer Part Number
S201MB40
Description
MCB, 1 POLE, 40A, 10KA, B CURVE
Manufacturer
ABB
Series
System Pro M Compactr
Datasheet

Specifications of S201MB40

No. Of Poles
1
Voltage Rating Vac
230V
Mounting Type
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Approval Bodies
IEC/EN 60898, IEC/EN 60947-2, VDE 0641 Part 11, UL 1077, CSA
Current Rating
40A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
System
pro M compact
Installation and operation instructions
Installation
Can be installed in any mounting position due to snap-on fixing to DIN rails EN 50 022, 35 mm width.
A If RCD F 200/FS 201 is installed without cross-wiring , hinge the upper part into the DIN rail and push to let the lower part of the device snap
B To release RCD F 200/FS 201 that are cross-wired with System pro M compact busbars, first remove the clamping screws. Then, pull the
C The busbar is deallocated and the RCD F 200/FS 201 can be pulled out by lifting the device forwards (2).
D The cross-wiring is re-inserted in the reverse order. First, open the clamping screws and pull out the quick fastener until it locks into place
Attention: Do not forget to re-tighten the clamping screws.
C Removal when
Connection
Feeder optional, top or bottom. Ensure that conductors are con-
nected correctly and firmly.
If the 4-pole RCCB is operated as a 2-pole RCCB, use terminals
5 and 7 or, as the case may be, 6 and 8 to make sure that the
test button function of the RCCB is working. In the case of a
three-phase system with U
terminals 4 and 8 must be bridged.
Operation
F 200/FS 201 is switched ON or OFF with the blue operating
lever.
22
A Assembly,
Operating test
To test proper functioning, press the blue test button when the device is switched ON, the RCCB must trip immediately (the knob jumps into
the „0“ switching position).
It is necessary to test the RCD halfyearly, if no other regional or user specified additional test are required.
pro M compact
cross wiring
remains in place
disassembly
without
pro M compact
cross wiring
into place (1). The device is released in the reverse order, after the quick fastener has been removed with a screw driver (2).
lower part of the F 200/FS 201 forwards (1) and lift it straight up (1a), then, the quick fastener will recede (1b).
for the first time (3). Then, take the RCD F 200/FS 201 and insert it with the rear terminal side onto the pins of the System pro M compact
busbar (4), turn it into the direction of the DIN rail (4a) and shift it vertically downwards (4b), to let the quick fastener snap back into place
(4c).
quick
fastener
pro M compact
busbar
snap on
pin
n
®
= 127/230 V (without neutral N),
Residual-current-operated circuit-breakers
F 200 series/FS 201
release
D Insertion when
pro M compact
cross wiring
remains in place
B Detaching when
pro M compact
cross wiring
remains in place
pin
pro M compact
busbar
pro M compact
busbar