Description
MCB, 1 POLE, 40A, 10KA, B CURVE
Manufacturer
ABB
Series
System Pro M Compactr
Datasheet

Specifications of S201MB40

No. Of Poles
1
Voltage Rating Vac
230V
Mounting Type
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Approval Bodies
IEC/EN 60898, IEC/EN 60947-2, VDE 0641 Part 11, UL 1077, CSA
Current Rating
40A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
System
pro M compact
Tripping diagrams
Reading example for tripping characte-
ristic of the B-type trip characteristics
(in connection with the table
tripping characteristics on page 9, line B)
a
b
trip characteristic: D
I
S 200 MCBs
n
Thermal tripping characteristic:
Conventional non-tripping current
I
The MCB maintains the 1.13 times
of the rated current for at least
60 minutes.
Conventional tripping current
I
The MCB switches off within
60 minutes when the 1.45 times
of the rated current is reached.
Electromagnetic trip characteristic
AC:
The MCB maintains current rushes of
the 3-fold of the rated current for
more than 0.1 sec. (in this example
up to ca. 4 sec.).
The MCB switches off within less than
0.1 sec when the 5-times of the rated
current is reached.
= 0.5 ... 63 A
1
2
= selected non-tripping current
= selected tripping current.
®
Note:
Miniature circuit-breakers
S 200/S 200 M series
Deviating ambient temperature values and interdependencies need
to be taken into account
trip characteristic: B
I
S 200/S 200 M MCBs
n
= 6 ... 63 A
trip characteristic: K
I
S 200 MCBs
n
= 0.5 ... 63 A
trip characteristic: C
I
S 200/S 200 M MCBs
n
trip characteristic: Z
I
S 200 MCBs
= 0.5 ... 63 A
n
= 0.5 ... 63 A
11