Datasheet

Specifications of S201MB40

No. Of Poles
1
Voltage Rating Vac
230V
Mounting Type
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Approval Bodies
IEC/EN 60898, IEC/EN 60947-2, VDE 0641 Part 11, UL 1077, CSA
Current Rating
40A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
System
pro M compact
2. Mounting more than one S2C-S/H6R
Up to three S2C-H6R can be mounted.
Note: one signal contact max. fitted at first to MCB or RCCB
If fitted to an MCB, remove the bottom coupling pin (RCD), if fitted to an RCCB, remove the middle coupling pin (MCB), switch all signal
contact/ auxiliary switches to the end position ON, plug them together and carry through a function control test.
Function control test:
After all signal contacts/auxiliary switches or auxiliary switches have been mounted, use the upper coupling pin to switch on the devices
(ON position). If the lower (for RCD) or, as the case may be, the middle (for MCB) coupling pin is operated, all devices must trip.
Now combination with MCB/RCCB:
RCCB or MCB must be in the ON position
in ON position
Test functions of the signal contact
in ON and OFF position after hand operation
in ON position after tripping
18
Installation:
1. Mounting one S2C-S/H6R
switch in ON position
RCCB or MCB must be in the ON position
if fitted to MCB, remove bottom (RCD), if fitted to RCCB middle (MCB) coupling pin
if fitted to MCB, remove bottom (RCD), if fitted to RCCB middle (MCB) coupling pin
SK 0287 Z 02
®
Supplementary devices
remove coupling cover on the right side of the MCB/RCCB
remove coupling cover on the right side of the MCB/RCCB
SK 0285 Z 02
Test functions of the auxiliary switch
in ON position
in OFF position
SK 0288 Z 02
plug devices together.
signal contact/auxiliary switch
signal contact/auxiliary
plug devices together.