E53-QN Omron, E53-QN Datasheet - Page 8

no-image

E53-QN

Manufacturer Part Number
E53-QN
Description
OUTPUT UNIT SSR DRIVER 12VDC NPN
Manufacturer
Omron
Datasheet

Specifications of E53-QN

Accessory Type
Output Unit - Pulse (PNP) 12V Dc
Voltage Rating
12VDC
Current Rating
40mA
Svhc
No SVHC (15-Dec-2010)
No. Of Analogue Outputs
1
For Use With
E5EN-H And E5AN-H Controllers
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Characteristics
✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of
✽2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
✽3. K thermocouple at −100°C max.: ±10°C max.
✽4. External communications (RS-232C, RS-485, or RS-422) and cable communications for the Setup Tool can be used at the same time.
8
Indication accuracy
Transfer output accuracy ±0.3% FS max.
Influence of temperature
✽2
Influence of voltage ✽2
Input sampling period
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Affect of signal source
resistance
Insulation resistance
Dielectric strength
Vibration
resistance
Shock
resistance
Weight
Degree of protection
Memory protection
Setup Tool
Setup Tool port
Standards
EMC
−100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a
temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication
accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is
±0.3% of PV or ±3°C, whichever is greater, ±1 digit max.
The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1 digit max.
Advanced Digital Temperature Controller
Malfunction 10 to 55 Hz, 20 m/s
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s
Destruction 300 m/s
E5AN-H
E5EN-H
Approved
standards
Conformed
standards
Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1
Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max.
Analog input: ±0.1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Potentiometer input: ±5% FS ±1 digit max.
Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. ✽3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: (±1%FS) ±1 digit max.
60 ms
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
0.0 to 3240.0 s (in units of 0.1 s)
0.0 to 3240.0 s (in units of 0.1 s)
0.5, 1 to 99 s (in units of 1 s)
0.0 to 100.0% (in units of 0.1%)
−19999 to 32400 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
20 MΩ min. (at 500 VDC)
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g
Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g
Front panel: IP66, Rear case: IP20, Terminals: IP00
Non-volatile memory (number of writes: 1,000,000 times)
CX-Thermo version 4.0 or higher
Provided on the bottom of the E5AN-H and E5EN-H.
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN-H and E5EN-H.
Provided on the front of the E5AN-H and E5EN-H. An E58-CIFIR USB-infrared Conversion Cable is required to
connect the computer to the E5AN-H or E5EN-H. ✽4
UL 61010-1, CSA C22.2 No. 1010-1
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI:
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EMS:
ESD Immunity:
Electromagnetic Field Immunity:
Burst Noise Immunity:
Conducted Disturbance Immunity:
Surge Immunity:
Power Frequency Magnetic Field Immunity:
Voltage Dip/Interrupting Immunity:
2
2
, 3 times each in X, Y, and Z directions
, 3 times each in X, Y, and Z directions
2
for 10 min each in X, Y, and Z directions
E5AN-H/E5EN-H
EN 61326
EN 55011 Group 1, class A
EN 61326
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 61000-4-8
EN 61000-4-11
EN 61000-4-5

Related parts for E53-QN