E53-QN Omron, E53-QN Datasheet - Page 5

no-image

E53-QN

Manufacturer Part Number
E53-QN
Description
OUTPUT UNIT SSR DRIVER 12VDC NPN
Manufacturer
Omron
Datasheet

Specifications of E53-QN

Accessory Type
Output Unit - Pulse (PNP) 12V Dc
Voltage Rating
12VDC
Current Rating
40mA
Svhc
No SVHC (15-Dec-2010)
No. Of Analogue Outputs
1
For Use With
E5EN-H And E5AN-H Controllers
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Specifications
Ratings
Power supply voltage
Operating voltage range
Power consumption
Sensor input
Input impedance
Control method
Control
output
Auxiliary
output
Event
input
Logic
opera-
tions
Transfer
outputs
RSP
input
Setting method
Indication method
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Relay output
Voltage output
(for driving SSR)
Current output
Linear voltage output
Built-in SSR output
Relay output for posi-
tion-proportional con-
trol
Number of outputs
Output specifications
Number of outputs
External contact input
specifications
Number of operations 8 max.
Operations
Output
Work bit
assignment
Number of outputs
Output specifications
Number of inputs
Signal type
Analog input scaling
Accuracy
Input sampling period 60 ms
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
100 to 240 VAC: 12 VA
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)
Any of the following can be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
ON/OFF control or 2-PID control (with auto-tuning)
Output Unit (Install the Output Unit (sold separately).)
75 to 250 VAC, 1 A (resistive load)
Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations
min.
Potentiometer input: Must be between 100 Ω and 2.5 kΩ for maximum open position.
2 or 3 max.
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
5 V, 10 mA
2 (standard) or 4 (with an E53-AKB)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
• Logic operation:
• Delay:
• Output inversion: Possible
One work bit per operation
Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations,
auxiliary outputs, or control outputs.
1 max. (Depends on model. Models with transfer output (F in model number)
Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000
1
Current input: 4 to 20 mA (input impedance: 150 Ω ±10%)
Scaling of signal to engineering units (EU)
−19,999 to 30,000 (display: 30,000 max.)
(±0.2% of FS) ±1 digit max.
Set digitally using keys on the front panel or by using the RSP input.
11-segment digital display and individual indicators (7-segments display emulation also possible)
Character height: E5AN-H: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-H: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm
Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain
Number of digits: 5 for PV and SV, 4 for MV
Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection,
40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions,
control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic
operations, automatic cooling coefficient adjustment
−10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
25% to 85%
−25 to 65°C (with no condensation or icing)
Advanced Digital Temperature Controller
Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C,
and D are four inputs.)
ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
E5AN-H/E5EN-H
5

Related parts for E53-QN