TLR5 TDK Corporation, TLR5 Datasheet - Page 25

RACK 19" FOR TLRBP

TLR5

Manufacturer Part Number
TLR5
Description
RACK 19" FOR TLRBP
Manufacturer
TDK Corporation
Series
TLr
Datasheets

Specifications of TLR5

Accessory Type
Rack System
External Width
18.9"
Rack U Height
2
External Depth
14"
External Height
3.45"
Weight
7lb
For Use With
285-1646 - PWR SUP FNT END 48V 1000W 20A285-1645 - PWR SUP FNT END 24V 1000W 40A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
TL Series
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
285-1647

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
TLR516
Manufacturer:
KODENSHI
Quantity:
2 500
7 Troubleshooting
7.1 Problems and Solutions
The modular, plug-n-play nature of this plant makes diagnostics and repair very easy. Make sure
that all power modules are properly seated and latched into their respective slots. Make sure that
all power and signal connectors are properly mated. Table 13 lists problems and potential solutions.
7.2 Short circuit & Current Limit
ILimit can be adjusted up to +105% of the rated current of the power module. The system voltage
will remain constant up to ILimit at which point the system voltage will drop quickly toward 0 VDC,
as in Figure 15. Once a 24V or 48V power module drops below 12 VDC for more than 5 seconds,
the system will shut down. For a 12V system, once the power module drops below 4V for more than
60 seconds, the system will shut down. The system will automatically restart after 60 seconds, and
will continue until the short circuit is cleared.
3055 Del Sol Blvd • San Diego, CA 92154 • 1-800-LAMBDA-4
Problems and Solutions
Problem
DC OK LED extinguished or
Module DC fail via alarm cable
AC OK LED Extinguished or
Module AC fail via alarm cable
Thermal Limit Failure
Figure 15 - Short Circuit & Current Limit
Table 13 - Problems and Solutions
Solution
Replace bad power module unit - unlatch, remove and replace with spare.
System short circuit - inspect and replace load and wiring.
Reset commercial circuit breaker to the dedicated AC circuit that feeds system.
Seek alternative power source until power is restored.
Power module has shut down because it has exceeded the maximum rated
temperature. The power modules will automatically restart.
TLR5-S S ERIES POWER SYSTEM
Revision 1 : January 2006
Page. 25