ZUP120-3.6/U TDK Corporation, ZUP120-3.6/U Datasheet - Page 48

PWR SUP BENCH PROG 0-120V 432W

ZUP120-3.6/U

Manufacturer Part Number
ZUP120-3.6/U
Description
PWR SUP BENCH PROG 0-120V 432W
Manufacturer
TDK Corporation
Series
ZUPr
Type
Enclosedr
Datasheets

Specifications of ZUP120-3.6/U

Number Of Outputs
1
Efficiency
87%
Voltage - Output
0 ~ 120V
Power (watts)
432W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
0 ~ 120 VDC @ 3.6A
Size / Dimension
13.78" L x 4.88" W x 2.76" H (350mm x 124mm x 70mm)
Power (watts) - Rated
432W
Operating Temperature
0°C ~ 50°C
Approvals
CE, EN, UL
Line Regulation
0.01%
Load Regulation
0.01%
Output Current (max)
3.6A
Input Voltage
85 to 265V
Input Frequency
47 to 63Hz
Screening Level
Commercial
Operating Temperature Min Deg. C
0C
Operating Temperature Max Deg. C
50C
Mounting Style
Desktop
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / RoHS Status
Compliant, Lead free / RoHS Compliant
Other names
285-1672
ZUP1203.6/U
5.5.2 ID control commands
5.5.1 Initialization control
4
3
#
1
2
#
1
2
:ADRn;
:RMT?;
Commands
Commands
:RMTn;
:MDL?;
:REV?;
:DCL;
Returns the remote/local setting. The returned data is an ASCII string.
RM1 (The unit is in remote mode)
RM2 (The unit is in latched remote mode)
Sets the power supply address. ADR is followed by the address
which can be 01 to 31.
Sets the power supply to local or remote mode. (This command is active
when the unit is either in Local or Remote modes).Transition from Local to
Remote mode is made via the front panel only.
:RMT0; Transition from Remote to Local mode.
:RMT1; Transition from latched Remote to non-latched Remote.
:RMT2; Latched remote: Transition back to Local mode or to non- latched
Remote can be made via the serial port (RS232/485).
At this mode, the front panel Local/Rem function is disabled. Escape from
this mode to non -latched remote mode can be made by turning the AC
ON/OFF to OFF and after approx. 10sec.to ON again.
Returns the power supply model identification as an ASCII string:
Nemic-Lambda ZUP(XXV)-(YYA).
XX - The rated output voltage
YY - The rated output current
example: Nemic-Lambda ZUP(6V-33A)
Returns the software version as an ASCII string:
Ver XX-YYA.B
XX- The rated output voltage
YY- The rated output current
A.B- Version identifier
example: Ver 6-33 1.0
Clears the communication buffer and the following registers:
1. Operational status register
2. Alarm (fault) status register
3. Programming error register
Description
Description

Related parts for ZUP120-3.6/U