FPS100048 TDK Corporation, FPS100048 Datasheet - Page 14

PWR SUP FNT END 48V 1008W 21A

FPS100048

Manufacturer Part Number
FPS100048
Description
PWR SUP FNT END 48V 1008W 21A
Manufacturer
TDK Corporation
Series
FPSr
Type
Commercialr
Datasheets

Specifications of FPS100048

Power Supply Type
Switching (Closed Frame)
Voltage - Output
48V
Number Of Outputs
1
Power (watts)
1000W
Applications
Commercial
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 21A
Size / Dimension
1.61" L x 5" W x 11.4" H (40.9mm x 127mm x 289.6mm)
Power (watts) - Rated
1008W
Operating Temperature
0°C ~ 70°C
Efficiency
88%
Approvals
CE, EN, UL
Line Regulation
0.4%
Load Regulation
0.8%
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
48V
Output Current
21A
Power Rating
1kW
Input Voltage
85V AC To 265V AC / 120V DC To 360V DC
Maximum Output Current
21 A
Maximum Output Power
1008 W
Input Frequency
47 to 63 Hz
Brand/series
FPS1000 Series
Configuration
Enclosed
Operation
Linear
Output
48 VDC @ 21 A
Power, Output
1008 W
Primary Type
AC-DC
Special Features
High Efficiency, Hot Swappable, PFC, Remote On/Off, Remote Sense
Voltage, Input
85 to 265/120 to 360 VAC/VDC
Voltage, Output
48 VDC
Output Current (max)
21A
Screening Level
Commercial
Product Depth (mm)
127mm
Operating Temperature Min Deg. C
0C
Operating Temperature Max Deg. C
70C
Mounting Style
Screw
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1239

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
FPS100048/PS
Manufacturer:
TDK-LAMBDA
Quantity:
232
CHAPTER 4 FUNCTIONS AND FEATURES
4.1 Input Voltage Range
Input voltage is single phase 85~265Vac (47~63Hz). The power supply can be operated also with a DC input voltage,
120~330VDC but the safety approvals apply to the AC voltage only. Input voltage which is out of the specifications
might cause damage to the unit.
4.2 Output voltage trimming
The output voltage can be adjusted within the specifications via the V_Trim pin at the In/Out connector.
Refer to Fig 4-1 typical connection and calculation of the adjustment resistors:
Note that the Over Voltage Protection may trigger if the output voltage exceeds the maximum voltage specification.
4.3 Over Voltage Protection (OVP)
The OVP triggers when the output voltage exceeds the maximum rating and reaches the OVP limit. When the OVP
is triggered, the output voltage shuts down. In order to resume operation, the AC input voltage should be removed
for more than 30 sec. The OVP level is factory set and is not adjustable.
4.4 Over Current Protection (OCP)
A constant current limiting with automatic recovery is provided. The OCP operates when the output current exceeds
105%~125% of the rated output current. The output voltage recovers automatically when the overload condition is removed.
Avoid operating the power supply under overload condition for long time as it might cause damage to the power
supply.
4.5 Over Temperature Protection (OTP)
The OTP is activated when the ambient temperature or the power supply internal temperature exceeds a safe temperature.
When the OTP is activated, the power supply output shuts down. The output recovers automatically when the ambient
temperature or the internal temperature cools to a safe limit.
4.6 Auxiliary 12V output
An isolated 11.2V~12.5V output is provided (Referenced to the Signals_Return potential). The maximum output
current from this output is 0.25A. This output has a built-in Oring diode to allow paralleling FPS1000 units. Use this
output for the control and monitoring signals described in this chapter or to operate application circuits.
4.7 Over Temperature Alarm
An open collector output provides an Over Temperature Alarm approx. 10°C below shut down by the OTP. The open
collector output is referenced to the Signals_Return potential and is isolated from the power supply +V and -V
terminals
The maximum sink current is 10mA and the maximum external voltage is 15V.
Refer to Fig 4-2 for typical application.
Fig 4-1
Fig 4-2
FPS1000
FPS1000
12
10
16
14 V_trim
13
8
+S
Over temperature alarm
Signals return
-S
12V aux
+V
-V
11
R1 KΩ
R2 KΩ
10KΩ
R1(K Ω )=20(K Ω )-R2(K Ω Ω)
FPS1000-12:
R2=0.0324*V
R1(K Ω )=5(K Ω )-R2(K Ω )
FPS1000-24:
R2=0.0785*V
R1(K Ω )=20(K Ω )-R2(K Ω )
FPS1000-32:
R2=0.0463*V
FPS1000-48:
R2=0.0497*V
R1(K Ω )=50(K Ω )-R2(K Ω )
FPS1000 Instruction Manual
2
2
2
2
out
out
out
out
-7.2795*V
-1.1298*V
-5.819*V
-4.5805*V
out
out
out
out
+105.132
+259.04
+9.9342
+109.49