2811271 Phoenix Contact, 2811271 Datasheet - Page 13

PROGRAMING ADAPTER USB INTERFACE

2811271

Manufacturer Part Number
2811271
Description
PROGRAMING ADAPTER USB INTERFACE
Manufacturer
Phoenix Contact
Datasheet

Specifications of 2811271

Accessory Type
IFS-USB-Programming Adapter
For Use With/related Products
UPS Systems
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
IFS-USB-PROG-ADAPTER
9
9.1
In mains operation (AC input voltage present) the output
voltage of the TRIO-UPS corresponds to the setting at the
potentiometer 4. In the event of supply voltage failure,
battery mode is activated without interruption. The output
voltage is now directly dependent on the battery voltage and
is U
9.2
If the connected load cannot be supplied from the power
storage device in the event that the AC voltage fails, the
UPS can be disabled via R1/R2. This shutdown can be
performed during mains operation or while battery mode is
active.
UPS active, remote shutdown deactivated, default upon
delivery:
9.3
The time after which battery mode is exited is set via the "
selector switch on the front of the device:
9.4
In "PC mode", the UPS function follows a chronological
sequence that can be parameterized via the software and
individually optimized for the relevant IPC solution.
Requirements: IFS-USB-PROG-ADAPTER data cable
(Order No. 2811271) and UPS-CONF software
(Order No. 2320403).
104103_en_00
BAT
Terminal points "R1" and "R2" are short circuited (with
plug-in bridges by default upon delivery) OR 24 V DC is
present at terminal point "R2".
If the supply voltage fails, the TRIO-UPS switches to
battery mode. UPS not active, remote shutdown
activated:
Terminal points "R1" and "R2" are not short circuited
AND 0 V DC is present at terminal point "R2".
All LEDs are OFF.
If the supply voltage fails, the TRIO-UPS does not
switch to battery mode, the device shuts down.
The connected loads are supplied and the
rechargeable battery module is charged as long as the
supply voltage is present.
0.5 to 20 minutes
Parameterizable time via software
("CUSTOM" switch position, default: 0.5 minutes)
Unlimited (buffering with the total stored energy)
PC mode (see Section 9.4 "PC mode" )
Method of operation
Output voltage
Remote shutdown
Buffer time setting
PC mode
- 0.5 V.
To set the parameters, an Interface interface (IFS) is used
for data exchange between the TRIO-UPS and a suitable
user interface on the IPC. The user is supported by help
texts and graphics for the individual parameters.
As an option, parameterization can be carried out using an
IFS-CONFSTICK. Here, a parameter record is transferred
from the TRIO-UPS to the IFS-CONFSTICK. This
parameter record can then be written to any other
TRIO-UPS.
In "PC mode", the UPS function follows a parameterizable
chronological sequence of delay time, IPC shutdown, and
IPC idle time.
Delay time:
If the mains voltage is not applied again within the first 60
seconds of battery mode, for example, "Bat.-Mode" is
indicated in order to shut down an IPC with a delay.
IPC shutdown:
Shutdown is performed via a data cable to the IPC. The IPC
must be connected to the UPS via a USB data cable.
The IPC is supplied by the TRIO-UPS for a parameterizable
period of time, e.g., 2 minutes.
TRIO-UPS/1AC/24DC/5
PHOENIX CONTACT
13