AOM-MUXF GAMEWELL-FCI [Gamewell-FCI by Honeywell], AOM-MUXF Datasheet

no-image

AOM-MUXF

Manufacturer Part Number
AOM-MUXF
Description
Telephone monitor module
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Description
AOM-MUXF
The Gamewell-FCI Velociti
ule (AOM-MUXF) is used in dual-channel bulk audio sys-
tems to select the alarm tone and/or recorded voice
message to be transmitted to each evacuation zone. It
provides a notification appliance circuit that is controlled by
either channel audio source and can be configured as
Class B, Style Y or Class A, Style Z.
The notification appliance circuit can transfer up to 63
watts of audio power to its speakers. The AOM-MUXF
module installs in the signaling line circuit of the
Gamewell-FCI emergency voice evacuation systems. The
AOM-MUXF is designed to fit into a 4" (10.16 cm) square
junction box 2 1/8" (5.5 cm) deep.
AOM-TELF
The Gamewell-FCI Velociti
module
between the command center and the telephone jacks/
warden stations. Wiring to individual telephone jacks and
handsets is supervised and may be configured as two-wire
(Class B), or fault tolerant, (Class A). Status is reported to
the panel as NORMAL, TROUBLE, or TELEPHONE. The
module contains a panel-controlled LED indicator.
The AOM-TELF installs in the signaling line circuit of the
Gamewell-FCI emergency voice evacuation systems. The
AOM-TELF is designed to fit into a 4" (10.16 cm) square
junction box 2 1/8" (5.5 cm) deep.
The Velociti
substantially increases the speed of communication
between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate in
a grouped fashion. If one of the devices in the group has a
status change, the panel’s microprocessor stops the group
poll and concentrates on the single device. The net effect
is response speed up to five times greater than earlier
designs.
Ordering Information
Model
AOM-TELF
AOM-MUXF
Velociti
Inc.
©2008 Honeywell International Inc. All rights reserved.
®
and E3 Series
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
(AOM-TELF)
®
Series use a communication protocol that
®
are registered trademarks of Honeywell International
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
controls
Description
Telephone monitor module
Multiplex output module
®
®
Series, multiplex output mod-
Series, telephone monitor
the
communications
www.gamewell-fci.com
GAMEWELL-FCI
AOM-MUXF, AOM-TELF
Addressable Audio Evacuation Modules
Features
• Compact size allows easy installation.
• AOM-MUXF can transfer up to sixty-three (63), watts of
• Class A, fault tolerant, or Class B wiring.
• Bicolor LEDs flash green whenever the module is
*Note: Only the red LED is operative in panels that do not operate
in Velociti
Specifications
Supervisory Current:
Alarm Current:
Operating
Temperature:
Relative Humidity:
Dimensions:
End-of-Line Resistance: AOM-TELF—3.9K
audio power
address, and light steady red on alarm.*
®
Velociti
mode.
SIGNALIN G
An ISO 900 1-20 00 Com pa ny
S1949
AOM-MUX, AOM-TELF
APPROVED
3023594
FM
AOM-MUXF .00035 A
AOM-TELF .0024 A
AOM-MUXF .0075 A
AOM-TELF .0075 A
32° to 120° F (0° to 49° C)
10 to 93% relative humidity
(non-condensing)
4 1/2” H x 4” W x 1 1/4” D
(11.4 H x 10.16 W x 3.2 D cm)
AOM-MUXF—47K ohms
227-03-E Vol.IV
9020-0628 Rev. C2 page 1 of 1
MEA
Approved
®
07300-0694:178