AOM-2SF GAMEWELL-FCI [Gamewell-FCI by Honeywell], AOM-2SF Datasheet

no-image

AOM-2SF

Manufacturer Part Number
AOM-2SF
Description
Addressable output supervised control module
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Description
Velociti
UL
The Gamewell-FCI Velociti
supervised
Gamewell-FCI analog addressable fire alarm control to
switch an external power supply, such as a DC supply or
audio amplifier (up to 80 VRMS) to notification appliances.
The AOM-2SF notification appliance circuit can be wired
either Class A (Style Z) or Class B (Style Y). It also super-
vises the wiring to the connected loads and reports their
status to the panel as NORMAL, OPEN or SHORT CIR-
CUIT. The module contains a panel controlled LED.
The Velociti
substantially increases the speed of communication
between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate in
a grouped fashion. If one of the devices in the group has a
status change, the panel’s microprocessor stops the group
poll and concentrates on the single device. The net effect
is response speed up to five times greater than earlier
designs.
The module is UL Listed as suitable for releasing device
service and FM Approved for deluge and preaction ser-
vice. Refer to the Gamewell-FCI Compatibility Addendum,
P/N 9000-0427, for a list of approved, compatible sole-
noids. The AOM-2SF module is designed for installation in
the signaling line circuit of any Gamewell-FCI analog
addressable control panel. The signaling line circuits of
Gamewell-FCI analog addressable control panels are
designed to accommodate up to 159 modules per circuit.
The AOM-2SF is designed to mount in a 4” (10.16 cm)
square junction box 2 1/8” (5.5 cm) deep.
Relay Contact Ratings
Current
Rating
3A
2A
0.9A
0.5A
0.5A
1A
0.5A
0.7A
®
©2008 Honeywell International Inc. All rights reserved.
is a registered trademark of Underwriters Laboratories Inc.
®
is a registered trademark of Honeywell International Inc.
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
Maximum
Voltage
30 VDC
30 VDC
110 VDC Resistive
125 VAC
30 VDC
30 VDC
125 VAC
75 VAC
®
control
Series use a communication protocol that
Load
Description
Resistive
Resistive
Resistive
Inductive (L/R=5ms) Coded
Inductive (L/R=2ms) Coded
Inductive (PF=.35) Non-Coded
Inductive
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
module
®
Series addressable output
(AOM-2SF)
Application
Non-Coded
Coded
Non-Coded
Non-Coded
Non-Coded
allows
www.gamewell-fci.com
an
GAMEWELL-FCI
Features
• Compact Size allows easy installation
• Class A, Style Z, or Class B, Style Y notification
• Will accommodate audio amplifiers up to 80 V
• Listed as suitable for releasing device service
• Bicolor LEDS flash green whenever the module is
*Note: Only the red LED is operative in panels that do not operate in
Velociti
Specifications
Supervisory Current: .000375 amps.
Alarm Current:
Operating
Temperature:
Relative Humidity:
Dimensions:
Ordering Information
Model
AOM-2SF
appliance circuit
addressed, and lights steady red on alarm*
®
mode.
Velociti
Supervised Control Module
SIGNALING
An ISO 9001-2000 Company
S1949
Addressable Output Relay
APPROVED
3023594
.0065 amps.
32° to 120° F (0° to 49° C)
10 to 93% relative humidity
(non-condensing)
4 1/2” H x 4” W x 1 1/4” D
(11.4 H x 10.2 W x 3.2 D cm)
Description
Addressable output supervised
control module
FM
AOM-2SF
227-03-E Vol.IV
MEA
Approved