AOM-2RF GAMEWELL-FCI [Gamewell-FCI by Honeywell], AOM-2RF Datasheet

no-image

AOM-2RF

Manufacturer Part Number
AOM-2RF
Description
Addressable output relay control module
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Description
The Gamewell-FCI Velociti
relay control module (AOM-2RF) allows an Gamewell-FCI
analog addressable fire alarm control to switch discrete
relay contacts by code command. The relay provides two
(2), isolated sets of Form-C contacts which transfer simul-
taneously. Circuit connections to the relay contacts are not
supervised by the module.
The Velociti
substantially increases the speed of communication
between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate in a
grouped fashion. If one of the devices in the group has a
status change, the panel’s microprocessor stops the group
poll and concentrates on the single device. The net effect is
response speed up to five times greater than earlier
designs.
The AOM-2RF Module is designed for installation in the
signaling line circuit of any Gamewell-FCI analog address-
able fire control panel. The module contains a panel con-
trolled LED. The AOM-2RF is designed to mount in a 4”
square junction box 2 1/8” deep.
Velociti
Relay Contact Ratings
Current
3A
2A
0.9A
0.5A
0.5A
1A
0.5A
0.7A
Rating
©2008 Honeywell International Inc. All rights reserved.
®
Series is a registered trademark of Honeywell International Inc.
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
®
Maximum
30 VDC
30 VDC
110 VDC
125 VAC
30 VDC
30 VDC
125 VAC
75 VAC
Voltage
Series use a communication protocol that
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Description
Resistive
Resistive
Resistive
Resistive
Inductive
(L/R=5ms)
Inductive
(L/R=2ms)
Inductive
(PF=.35)
Inductive
®
Load
Series, addressable output
Non-Coded
Non-Coded
Coded
Non-Coded
Non-Coded
Coded
Coded
Non-Coded
Application
www.gamewell-fci.com
GAMEWELL-FCI
Features
• Two (2) sets of Form “C” contacts
• Visual rotary, decimal switch addressing (01-159)
• Bicolor LEDs flash green whenever the sensor is
• Compact size allows easy installation
Note: Only the red LED is operative in panels that do not operate
in Velociti
Specifications
Supervisory current:
Alarm current:
Operating temperature: 32° to 120° F (0° to 49° C)
Relative humidity:
Dimensions:
Ordering Information
Model
AOM-2RF
addressed, and light steady red on alarm*
®
Velociti
mode.
SIGNA LIN G
A n I S O 9 0 0 1 - 2 0 0 0 C o m p a n y
S1949
Addressable Output Relay
Description
Addressable output relay control module
A PPRO VED
3023594
FM
AOM-2RF
227-03-E Vol.IV
.000375 amps.
.0065 amps.
10 to 93% relative humidity
(non-condensing)
4 1/2” H x 4” W x 1 1/4”
(11.4 x 10.2 x 3.2 cm)
MEA
Approv ed
9020-0625 Rev. D1 page 1 of 1
AOM-2RF
®
Control Module
07300-0694:178
Series

Related parts for AOM-2RF

Related keywords