C200H-ATTA3 Omron, C200H-ATTA3 Datasheet - Page 93

no-image

C200H-ATTA3

Manufacturer Part Number
C200H-ATTA3
Description
I/O LOCK BRACKT 10-SLOT
Manufacturer
Omron
Datasheet

Specifications of C200H-ATTA3

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
C200HATTA3
Error Messages
Communications Errors
Fatal Operating Errors
Power interruption
CPU error
Memory error
No END(01) instruction
I/O bus error
No message.
No message.
MEMORY ERR
NO END INST
I/O BUS ERR
Error and message
The COMM or COMM 1 indicator will go out for errors in communications be-
tween the peripheral port and a peripheral device and COMM 2 will will go out for
errors in communications between the RS-232C port and a peripheral device. If
an error is indicated, check the communications path and the C200HS program.
The ports can be reset using the Peripheral Port Reset Bit (SR 25208) and the
RS-232C Port Reset Bit (SR 25209).
The following error messages appear for errors that occur after program execu-
tion has been started. PC operation and program execution will stop and all out-
puts from the PC will be turned OFF when any of the following errors occur. No
CPU indicators will be lit for the power interruption error. For all other fatal oper-
ating errors, the POWER and ALM/ERR indicators will be lit. The RUN output will
be OFF.
Rack no.
*
00
None
F1
F0
C0 to C2 Error has occurred in
FAL no.
Power has been
interrupted for at least
10 ms.
Watchdog timer has
exceeded maximum
setting (default setting:
130 ms).
SR 27211 ON:
A checksum error has
occurred in the PC
Setup (DM 6600 to
DM 6655).
SR 27212 ON:
A checksum error has
occurred in the program,
indicating an incorrect
instruction.
SR 27213 ON
A checksum error has
occurred in an
expansion instruction
change.
SR 27214 ON:
Memory Cassette was
installed or removed
with the power on.
SR 27215 ON:
Autoboot error.
END(01) is not written
anywhere in program.
the bus line between the
CPU and I/O Units.
Probable cause
Check power supply voltage
and power lines. Try to
power-up again.
Restart system in PROGRAM
mode and check program.
Reduce cycle time or reset
watchdog timer if longer time
required. (Consider effects of
longer cycle time before
resetting.)
Check the PC Setup.
Check the program.
Install the Memory Cassette
correctly.
Check whether the CPU
memory is protected or a
checksum error occurred in the
Memory Cassette.
Write END(01) at the final
address of the program.
The rightmost digit of the FAL
number will indicate the number
of the Rack where the error was
detected. Check cable
connections between the I/O
Units and Racks.
Possible correction
Section 6-4
79