MSO-0008P-012 NCC, MSO-0008P-012 Datasheet - Page 54

no-image

MSO-0008P-012

Manufacturer Part Number
MSO-0008P-012
Description
Socket, Relay; 8 Pin Octal
Manufacturer
NCC
Type
Octalr
Datasheet

Specifications of MSO-0008P-012

Number Of Contacts
8
Time Range
0.05 Sec. to 999 Min.
Output Rating
10 A @ 240 VAC Max.; 100 mA @ 5 VDC Min.
Operating Temperature
–23°C to +55°C
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
2-8
Resistance Sensors
Model NS141
FEATURES
Operating Logic: In Model NS141-A10
(Pump Down) the load is de-energized until
the liquid reaches the high probe. When liq-
uid touches the high probe, the load is acti-
vated until the level drops below the low
probe.
is energized until the liquid reaches the high
probe. When liquid touches the high probe,
the load is deactivated until the level drops
below the low probe.
when the load is off. If the tank is non-con-
ductive, a third (common) probe must be
installed at a level where it will always be
submerged.
SPECIFICATIONS
CONTROL TYPE
On/Off Resistance Sensing:
NS141-A10/A100: Probe resistance below set
point activates relay
NS141-B10/B100: Probe resistance above set
point activates relay
Sensing Voltage: 30 VAC, max. RMS
Sensing Current: 1 mA, max. RMS
Sensitivity Adjustment: Factory set at
50 K ohms, ±20%
ORDERING INFORMATION
Probe Holder with Ground
Pump Down
Pump Up
Pump Down
Pump Up
Model NS141-B10 (Pump Up): The load
On both models a red light is activated
100% functionally tested
16 A 1 hp solid state output rating
120/240, 100/200 VAC operation
voltages
Solid state sensing circuitry
Isolated UL Class ll sensing voltage
Adjustable sensitivity by Trimpot
1/4” male fast-ons for circuit connection
Conformal coating to protect circuit
from harsh environments
LIQUID LEVEL CONTROL SERIES
ACCESSORY
LOGIC TYPE
File #E61377
INPUT VOLTAGE
PART NUMBER
LLH-11383-010
120/240 VAC
120/240 VAC
100/200 VAC
100/200 VAC
(Dual Probe, Dual Voltage) 1hp Solid State Output
OUTPUT
Type: Single-pole solid state switch
Rating: 16 A 1 hp at 120, 240 VAC
Life:
Electrical: 1,000,000 min. at full load
INPUT
Operating Voltage:
NS141-A10: 120 VAC, ±10%, between COM
and 120 terminals
NS141-B10: 240 VAC, ±10%, between COM
and 240 terminals
NS141-A100: 100 VAC, ±10%, between COM
and 120 terminals
NS141-B100: 200 VAC, ±10%, between COM
and 240 terminals
Power Consumption:
NS141-A10/B10: 3.0 VA max.
NS141-A100/B100: 4.0 VA max.
Frequency: 50/60 Hz
PROTECTION
Isolation: 1500 VAC between probe and other
terminals
Transient Voltage: Protected by a 30 joule metal
oxide varistor
MECHANICAL
Terminations: 1/4” x .032” male fast-ons for
input voltage and load, .187” x .020” fast-ons for
probes
Mounting: 2 - 3/16” slots on 3.5” center in alumi-
num chassis
ENVIRONMENTAL
Operating Temperature: 0°C to 65°C
4608/12/94
16
12
8
4
0
075
075
MAXIMUM LOAD VS. AMBIENT
68 (20)
AMBIENT TEMPERATURE
104 (40)
075
140 (60)
075
LNC-NS141-A100
LNC-NS141-B100
LNC-NS141-A10
LNC-NS141-B10
PART NUMBER
F ( C)
176 (80)
075
075
075
075
12" X 12" HEATSINK
10" X 10" HEATSINK
6" X 6" HEATSINK
NO HEATSINK
075
.187 X .020 MALE
FAST-ON (3 PL)
OUTPUT WHEN 120V INPUT IS USED
MUST USE COM TO 240 V OUTPUT
NOTE: MUST USE COM TO 120 V
1.40
WHEN 240 V INPUT IS USED
COM
INPUT VOLTAGE
COM
.250 X .032 MALE
FAST-ON (6 PL)
2.80
120 VAC
240 VAC
120V
(RED LED)
120V
IDLE
240V
240V
LOAD