ES-UA-5A BANNER ENGINEERING, ES-UA-5A Datasheet - Page 17

no-image

ES-UA-5A

Manufacturer Part Number
ES-UA-5A
Description
Sensor, E-stop Module, output 6A,
Manufacturer
BANNER ENGINEERING
Type
Safetyr
Datasheets

Specifications of ES-UA-5A

Contact Form
4-NO/1-NC
Dimensions
45mmW×84mmH×118mmD
Enclosure Rating
IP20
Ip Rating
IP20
Mounting Type
DIN Rail
Number Of Outputs
8
Output Type
Relay
Power, Rating
4 W
Primary Type
Controller
Standards
UL, CSA, CE
Voltage, Supply
115/12 to 24 VAC/VDC
Coil Voltage Vdc Nom
24V
Coil Resistance
250ohm
Contact Current Max
6A
Contact Voltage Ac Nom
24V
Contact Voltage Dc Nom
250V
Contact Configuration
SPST-NC
No. Of Poles
1
Relay Mounting
DIN Rail
Lead Free Status / Rohs Status
RoHS Exempt Product
For Use With
Emergency Stop
ES-UA-5A and ES-VA-5A E-Stop Safety Modules
P/N 122365 rev. C
Condition
Fault
Fault
Fault
Fault
MSCs do not energize
Banner Engineering Corp. - Minneapolis, MN USA - www.bannerengineering.com
Indicator Status
Ch1 LED ON
Ch2 LED OFF
Power LED ON
Fault LED ON*
Ch1 and Ch2 LED flashing alter-
nately
Power LED ON
Fault LED ON*
Ch1 LED OFF
Ch2 LED Flashing
Power LED ON
Fault LED ON*
Ch1 LED Flashing
Ch2 LED OFF
Power LED ON
Fault LED ON*
Ch2 LED ON
Ch1 LED ON
All LEDs OFF
Dim LEDs
*Fault LED Flickers
Power LED ON
Fault LED OFF
Ch1 LED ON
Ch2 LED ON
Tel: 763.544.3164
Possible Causes / Solutions
Input concurrency fault: Both inputs did not open
concurrently. Both inputs are now closed.
Input concurrency fault: Ch1 opened and closed and
is now open while Ch2 remained closed.
Input concurrency fault: Ch1 remained closed while
Ch2 opened and closed and is now open.
Possible input fault: Ch1 and Ch 2 are closed and are
(or were) shorted together.
Possible internal fault:
Possible fault in machine control or wiring to mod-
ule:
Dim Power LED:
Other LEDs dim:
This is normal while the Fault LED is ON.
Possible fault in machine control or an open circuit
between machine control and MSCs:
Check switch.
Check connectors are properly seated.
Check switches/wiring at both inputs.
Open both inputs to clear the fault.
Check switches/wiring at both inputs.
Open both inputs to clear the fault.
Check switches/wiring at both inputs.
Open both inputs to clear the fault .
Check wiring at both inputs.
Open both inputs to clear the fault.
Return to factory for repair or replacement
Check input power connections or external fuses.
Check connectors are properly seated.
Check power supply capacity and load.
May glow during power-up (normal).
Check power supply load and capacity.
Check continuity of safety outputs (e.g. between termi-
nals 13 and 14).
Check control wires and connectors.
Check MSCs.
17