DTX-MFM2 FLUKE NETWORKS, DTX-MFM2 Datasheet - Page 61

DTX-MFM2 REPLACEMENT FOR DTX-MFM

DTX-MFM2

Manufacturer Part Number
DTX-MFM2
Description
DTX-MFM2 REPLACEMENT FOR DTX-MFM
Manufacturer
FLUKE NETWORKS
Datasheet

Specifications of DTX-MFM2

Multimode Fiber Module Set
ROHS COMPLIANT
1. Set Up the Tester
1-1 Turn on the tester. Wait for a minimum of 5 minutes
1-2 Turn the rotary switch to SETUP, then make these
ANSI/TIA-568-C
ISO/IEC 14763-3
for the tester to become stable. Wait for a longer time
if the tester is much colder or hotter than the work
area.
settings:
Standard
Test Limit: Select the applicable limit:
TIA-568-C
Multimode
ISO/IEC 14763-3
Test Limit for
Multimode
TIA-568-C
Singlemode ISP
ISO/IEC 14763-3
Test Limit for
Singlemode
Appendix A: How to Test Your Test Reference Cords
Fiber Type: Select the type of cable you will test. This
sets the index of refraction (n). The test limits shown
above use n to calculate the length of the fiber, then
they use the length to calculate the limit for loss.
Thus, you must use the correct value of n to get an
accurate measurement of loss. If you cannot find the
correct fiber type, you can enter the value of n for
your fiber on tab 3 of the setup menus. Get the
value of n from the cable vendor.
Remote End Setup: Loopback
Bi-Directional: Yes
Number of Adapters: 1
Connector Type: Select the type of connector that is
on the cords you will test
Test Method: 1 Jumper
55