DTX-MFM2/GFM2/SFM2 Fiber Modules
Users Manual
30
Autotest in Loopback Mode: Set the Reference
1
2
Turn on the tester and smart remote and let them sit for
5 minutes. Allow additional time if the modules have
been stored above or below ambient temperature.
Turn the rotary switch to SETUP, then select Fiber Loss.
Set the following on the Fiber Loss tabs (press
other tabs):
• Test Limit: Select the test limit required for the job.
• Fiber Type: Select the fiber type to be tested.
• Remote End Setup: Set to Loopback.
• Bi-directional: Enable this if you are required to test
• Number of Adapters and Number of Splices: Enter
Press
the fiber in both directions.
the number of adapters and splices that will be added
to each direction of the fiber path after the reference
is set.
J
More to see other lists of limits.
C
to see
3
4
See Table 2 on page 15 for details on settings.
• Connector Type: Select the connector type used in
• Test Method: Refers to the number of adapters
Turn the rotary switch to SPECIAL FUNCTIONS, then
select Set Reference. If both a fiber module and a
twisted pair or coaxial adapter are attached, select
Fiber Module next.
The Set Reference screen shows connections for the
test method you selected. Figure 12 shows connections
for the 1 Jumper method. Clean and inspect the
connectors on the tester and test reference cord,
connect the tester’s INPUT and OUTPUT ports; then
press
the cabling to be tested. Select General if the exact
type is not listed.
represented in the loss results. Select 1 Jumper if you
use the reference and test connections shown in this
manual.
P
.
-continued-