Specifications of DTX-MFM2

Multimode Fiber Module Set
ROHS COMPLIANT
SETUP > Fiber Loss >
Index of Ref. Source
(n) > User Defined or
Default
SPECIAL FUNCTIONS
> Set Reference
Patch Lengths
(softkey on the View
Connections screen)
Settings for saving
tests
Setting
The tester uses the index of refraction (n) defined in the currently selected fiber type (Default)
or a value you define (User Defined). The default value defined by the selected fiber type
represents the typical value for that fiber type. You may enter a different value if necessary. To
determine the actual value, change the index of refraction until the measured length matches
the known length of a fiber.
Increasing the index of refraction decreases the reported length.
Setting a reference sets the baseline power level for loss measurements. See “About Setting
the Reference” on page 11.
After you set the reference, you can enter the lengths of the test reference cords used. The
lengths are saved with results to meet TIA reporting requirements for fiber test results.
See the DTX Series CableAnalyzer Users Manual or Technical Reference Handbook for details
on preparing to save tests.
Table 2. Fiber Test Settings (cont.)
Description
Fiber Test Settings