CS1W-AD161 Omron, CS1W-AD161 Datasheet - Page 13

no-image

CS1W-AD161

Manufacturer Part Number
CS1W-AD161
Description
CS1 16 Pt Analog Inp Conn Type
Manufacturer
Omron
Datasheet

Specifications of CS1W-AD161

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Function Blocks (Unit Ver. 3.0)
Arithmetic
Functions
Time Function
Signal Selection/
Switching
ITEM Settings
18
Type
Addition or Subtraction
(See note 1.)
Multiplication (See note 1.) Performs multiplication with gain and bias on up to 2 analog signals.
Division (See note 1.)
Range Conversion
(See note 1.)
Arithmetic Operation
(See note 1.)
Square Root (See note 1.) Performs square root extraction (with low-end cutout) on single analog signals.
Absolute Value
(See note 1.)
Non-linear Gain (Dead
Band) (See note 1.)
Low-end Cutout
(See note 1.)
Segment Linearizer
(See note 1.)
Temperature And Pressure
Correction (See note 1.)
First-order Lag
(See note 1.)
Rate-of-change Limit
(See note 1.)
Moving Average
(See note 1.)
Lead/Delay (See note 1.)
Dead Time (See note 1.)
Dead Time Compensation Used for Smith’s dead time compensation PID control
Accumulator for Instanta-
neous Value Input
Run Time Accumulator
Time Sequence Data Sta-
tistics (See note 1.)
Ramp Program
Segment Program
Segment Program 2
Rank Selector (See note
1.)
Input Selector (See note 1.) Selects the specified analog signals specified by the contact signal from up to 8 analog sig-
3-input Selector (See note
1.)
3-output Selector
(See note 1.)
Constant Selector
(See note 1.)
Constant Generator
(See note 1.)
Ramped Switch
Bank Selector
(See note 2.)
Split Converter
(See note 2.)
Constant ITEM Setting
(See note 1.)
Variable ITEM Setting
(See note 1.)
Batch Data Collector
(See note 1.)
Block Name
Performs lead/delay operation on single analog signals.
Performs addition/subtraction with gain and bias on up to 4 analog signals.
Performs division with gain and bias on up to 2 analog signals.
Easily converts up to 8 analog signals simply by inputting the 0% and 100% input values and
0% and 100% output values.
Performs various math operation (trigonometric. logarithmic, etc.) on floating-point decimal
values converted (to industrial units) from up to 8 analog inputs.
Outputs the absolute value of single analog signals.
Performs non-linear (3 gain values) operation on single analog signals. Analog signals can
also set as a dead band (with different gap).
Sets output to zero close to the zero point of single analog signals.
Converts single analog signals to 15 segments before the signals is output.
Performs temperature and pressure correction.
Performs first-order lag operation on single analog signals.
Performs rate-of-change restriction on single analog signals.
Performs moving average operation on single analog signals.
Performs dead time and first-order lag operations on single analog signals.
Accumulates analog signals, and outputs 8-digit accumulated value signals.
Accumulates the operating time, and outputs the pulse signal per specified time.
Records time sequence data from analog signals and calculates statistics, such as averages
and standard deviations.
Ramp program setter for combining ramps for time and hold values.
Segment program setter setting the output values with respect to time.
Segment program setting with wait function for setting the output values with respect to time
Selects the rank of up to 8 analog signals.
nals.
Selects and outputs one of three analog input signals.
Outputs one analog input signal in one of three switched directions.
Selects 8 preset constants by the contact signal.
Outputs 8 independent constants.
Switches two analog inputs (or constants) with a ramp.
Stores a maximum of eight sets of PID parameters (SP, P, I, D, MH, ML) in advance, and
switches them to basic PID, advanced PID, or blended PID parameters in response to the
analog input zone or input bit.
Takes an operating amount input from a basic PID or advanced PID block and converts the
V characteristics or parallel characteristics into two analog outputs (e.g., heating and cooling
operating amounts).
Writes the constant to the specified ITEM at the rising edge of the send command contact.
Writes the analog signal to the specified ITEM at the rising edge of the send command con-
tact.
Stores each of max. 8 analog inputs to buffer by a certain timing within sequential process-
ing.
Function
Operation Blocks

Related parts for CS1W-AD161