Connecting to the RS-232C Port at the Host
CPU Unit Allocation DM Area Settings
Setting is written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocation DM area (system setting area) of
the CPU Unit. After the setting is written, it becomes effective by turning the
power ON, restarting the Unit, restarting the communications port, or execu-
tion of the STUP command.
In the following, the channel numbers of the allocation DM area and settings
are shown.
*1
When connecting PTs with model numbers 3 to 6 to port 1, for example, set
the value 8200 hex to DM32000, 0000 hex to DM32001, and 0006 hex to
DM32006.
Connecting to CS/CJ-series Serial Communications Unit
A CS/CJ-series Rack-mounting Unit:
Setting the Front Switches
Set the unit number of the Serial Communications Unit by using the rotary
switch located on the front panel. Set each switch with a flat blade screwdriver
so that the values or symbols in the setting value window agree with the fol-
lowing.
Allocation DM Area Settings for CPU Unit
Setting is written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocation DM area (system setting area) of
the CPU Unit. After the setting is written, it becomes effective by turning the
power ON, restarting the Unit, restarting the communications port, or execu-
tion of the STUP command.
In the following, the channel numbers of the allocation DM area and settings
are shown.
DM32000
DM32001
DM32006
m
m+1
m+6
Allocated DM Area words
Allocated DM Area words
Set any value between 0000 and 0009 hex for the baud rate. The same
baud rate will be used regardless of the value as long as it is between 0000
and 0009 hex.
Port 1
Port 1
Note Cannot be used with the CS1D-CPU65H/67H.
DM32010
DM32011
DM32016
m+10
m+11
m+16
RUN
ERC
SD1
RD1
SCU21
Port 2
Port 2
UNIT
No.
3 2
5 4
1 0
7 6
9 8
F E
RDY
ERH
SD2
RD2
A
D
C B
8200
0000 to 0009
000@
8200
0000 to 0009
000@
Set the unit number to 0 through F so
that it will not overlap with the numbers
used in other units.
Setting
Setting
(*1)
(*1)
m=DM30000+100*unit number (CH)
CS1W-SCU21,
CJ1W-SCU21(-V1)/41(-V1)
1:N NT Link Mode
Baud rate (standard)
connected PTs (0 to 7)
1:N NT Link Mode
Baud rate (standard)
connected PTs (0 to 7)
@ = The highest unit number of the
@ = The highest unit number of the
Setting Contents
Setting Contents
Section 4-1
69