Connecting to the Host’s RS-422A/485 Port
Reference:
Setting the Front Switches
C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1H, or SRM1
The connection method depends upon the model of PLC being used, as
shown in the following table.
I/O port selector switch
C200HX/HG/HE(-Z)E
CQM1H
CPM1
CPM2A, SRM1
CPM2C
• There are no Communications Boards for the C200HX/HG/HE(-Z)E in
• There are no Serial Communications Boards for the CQM1H in which port
which port B is the RS-422A port.
1 is the RS-422A port.
RS-232C
RS-422A
PLC model
• Connect to the RS-422A port (port A) on a Communica-
• Connect to the RS-422A port (port 2) on a Serial Commu-
• Connect to the peripheral port through a CPM1-CIF11 RS-
• Connect to the peripheral port through a CPM1-CIF11 RS-
• Connect to the peripheral port (on a CPM2C-CN111 or
(The CPM2C-CN111 splits the Unit’s communications port
into a RS-232C port and a peripheral port.)
tions Board.
nications Board.
422A Adapter.
422A Adapter.
CS1W-CN114 Connecting Cable) through a CPM1-CIF11
RS-422A Adapter.
• Host link communication method
• Communications type setting (DIP
• Host link default value settings
• Terminator setting (DIP SW6)
Connection method
For CPU Units manufactured from July
1995 onward (lot No. jj75), the stipulated
values in the DIP switch settings also are
9600 bps and 2 stop bits.
Set this to RS-422A.
(for host link communications)
selection (selector switch)
SW3) Set SW3 to OFF.
(DIP SW4)
Set this switch to ON.
(Set terminator ON.)
To effect the values set in the PLC
Setup, set SW4 to OFF.
To effect the existing DIP switch
settings, set SW4 to ON.
Note
For CPU Units manufactured before or
during June 1995 (lot No. jj65), the
existing DIP switch settings differ from
the PLC Setup default values as follows.
- Existing DIP switch settings:
- PLC Setup default values:
2,400 bps, 1 stop bit, even parity, 7 bit
data length
9,600 bps, 2 stop bits, even parity, 7 bit
data length
Section 5-2
103