XPSMCTS32 SQUARE D, XPSMCTS32 Datasheet - Page 128

no-image

XPSMCTS32

Manufacturer Part Number
XPSMCTS32
Description
SET OF SCREW TERMINALS
Manufacturer
SQUARE D
Datasheet

Specifications of XPSMCTS32

Accessory Type
Screw Connector
Rohs Compliant
Yes
Wiring diagrams
+
(1) Technical characteristics for maximum rating of fuses, see page 2/122.
(2) Only applicable to XPSMC32Zp.
tv = delay time
0 V
Input
Emergency stop 1
Input
Emergency stop 1
Input
Emergency stop 2
Input
Emergency stop 2
Input
Start
Output O1
Stop category 0
Output O2
Stop category 1
Key
Emergency stop monitoring, with or without time delay, 2-channel wiring, with start button
Category 4 conforming to standard EN 954-1.
Wiring diagram
Functional diagram
24 V
(1)
F1
0
A1
A2
C8 C7 C6 C5 C4 C3 C2 C1
T
1
Run
24 V
5 V
Emergency stop
Logic
GND
(continued)
A jumper between the two terminals of an emergency stop will not be detected.
Short-circuits between I1, I2, I3 will be detected.
GND
tv = 0…300 s
Emer.
stop
µC 1
µC 2
1
S1
GND
I1
I2
K0
Run
Chnl. 1
Chnl. 2
Emer.
stop
2
S2
I3
O1
Safety automation system solutions
Preventa™ configurable safety controllers
Type XPSMC
Chnl. 1
Chnl. 2
I4
Emergency stop
Start
S3
XPS MC
I5
O2
tv = 0…300 s
Chnl. 1
Chnl. 2
I6
… I16
O3
Chnl. 1
Chnl. 2
Run
Control
outputs
Sub-D 9
O4
Chnl. 1
Chnl. 2
Ter
O5
Chnl. 1
Chnl. 2
I17
(2)
O6
I32
K1
K2
13
14
Category 0 emergency stop
Category 1 emergency stop
23
24
K3
K4
H1
34
33
2/127
+
24 V
43
44
0 V
10
10
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9

Related parts for XPSMCTS32