CHARACTERISTICS
Environment
Approvals
Conforming to standards
Rated insulation voltage (Ui)
Rated impulse withstand voltage
(Uimp)
Safety separation of circuits SELV
Degree of protection:
Conforming to IEC/EN 60947-1
(protection against direct finger
contact)
Protective treatment
Ambient air temperature
around the device
Maximum operating altitude
Operating positions
Flame resistance
Environmental restrictions
Shock resistance
1/2 sine wave = 11 ms
Vibration resistance
5 to 300 Hz
Immunity to electrostatic discharge
Immunity to radiated
high-frequency disturbance
Immunity to fast
transient currents
Immunity to dissipated
shock waves
Immunity to conducted
high-frequency disturbance
© 2004 Schneider Electric All Rights Reserved
Conforming to IEC/EN 60947-1,
over voltage category III,
degree of pollution: 3
UL508, CSA C22-2 no. 14
Conforming to IEC/EN 60947-6-2
Conforming to IEC/EN 60947-1
appendix N
Front panel outside connection zone
Front panel and wired terminals
Other faces
Conforming to IEC/EN 60068
Conforming to IEC/EN 60068-2-30
Conforming to IEC/EN 60068-2-11
Storage
Operation
In relation to normal vertical
mounting plane
(Vac and Vdc control)
Conforming to UL 94
Conforming to IEC/EN 60695-2-12
Conforming to IEC/EN 60068-2-27
Conforming to IEC/EN 60068-2-6
Conforming to IEC/EN 61000-4-2
Conforming to IEC/EN 61000-4-3
Conforming to IEC/EN 61000-4-4
Conforming to IEC/EN 61000-4-5
Uc > 200 V
Uc < 200 V
Uc = 24 Vdc
Conforming to IEC/EN 61000-4-6
E164871 NKJH
E164862 NLDX, NLDX2
E164862 NLDX
meets the essential requirements of the LV and EMC
directives.
LU•B12, LU•B32
LU•S12, LU•S32 and Accessories
LUALB1
IEC/EN 60947-6-2, CSA C22-2 no. 14, Type E UL 508 Type E:
(LUtB12, LUtB32 with LU9SP0 incoming line phase barrier)
690 V
600 V
6 kV
Between the control or auxiliary circuit and the main circuit: 400 V
Between the control and auxiliary circuits: 400 V
IP 40 (Protection against direct contact with a 1 mm diameter wire)
IP 20 (Protection against direct finger contact)
IP 20 (Protection against direct finger contact)
“TH” (fungus resistant)
12 cycles
48 h
-40 to +185 °F (-40 to +85 °C)
Power bases with standard and advanced control units: -13 to +158 °F (-25
to +70 °C)
Power bases with multifunction control units:
At temperatures from -13 to +113 °F (-25 to +45 °C), gap not required
between products.
At temperatures from 113 °F (45 °C) to 131 °F (55 °C), allow a minimum
gap of 9 mm between products.
At temperatures from 131 °F (55 °C) up to 140 °F (60 °C), allow a minimum
gap of
0.79" (20 mm) between products.
6560 ft (2000 m)
V2
1760 °F (960 °C) (parts supporting live components)
1200 °F (650 °C)
Cadmium-free and silicone-free, recyclable
Power poles open: 10 gn
Power poles closed: 15 gn
Power poles open: 2 gn
Power poles closed: 4 gn
In open air: 8 kV—Level 3
On contact: 8 kv—Level 4
10 V/m—Level 3
All circuits except for serial link: 4 kV—Level 4
Serial link: 2 kV—Level 3
Common mode
4 kV
2 kV
2 kV
10 kV
LR43364 3211-08
LR43364 3211-04
LR43364 3211-08
30˚
30˚
LU•B12, LU•B32 and Accessories
LU•S12, LU•S32
LUALB1
Serial mode
2 kV
1 kV
0.5 kV
90˚
90˚
09/2004