E53-CK03 Omron, E53-CK03 Datasheet - Page 4

RS-485 OPTION E5CK

E53-CK03

Manufacturer Part Number
E53-CK03
Description
RS-485 OPTION E5CK
Manufacturer
Omron
Type
Temperature Controllerr
Datasheets

Specifications of E53-CK03

Rohs Compliant
YES
Accessory Type
RS-485 Communications Unit
Analog / Digital
Digital
Control Method
ON/OFF and PID Control
Voltage Rating
100 V to 240 V
Mounting
Panel
Counting Method
Up or Down (Selectable)
Size
100 mm L x 58 mm W x 48 mm H
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
E5CK
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
E53CK03
■ Characteristics
Note: The indication accuracy of the K1, T, and N thermocouples at a temperature of −100°C or less is ±2°C ±1 digit maximum. The indication
Indication accuracy (See note.)
Hysteresis
Proportional band (P)
Integral (reset) time (I)
Derivative (rate) time (D)
Control period
Manual reset value
Alarm setting range
Set time
Program capacity
Programming method
Time accuracy
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Degree of protection
Memory protection
Weight
EMC
Approved standards
accuracy of the U, L1, and L2 thermocouples at any temperature is ±2°C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is greater) ±1 digit
maximum.
The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or ±2°C, whichever is greater) ±1 digit maximum.
Thermocouple:
(±0.3% of indication value or ±1°C, whichever greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2% of indication value or ±0.8°C, whichever greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
0.01% to 99.99% FS (in units of 0.01% FS)
0.1% to 999.9% FS (in units of 0.1% FS)
0 to 3,999 s (in units of 1 s)
0 to 3,999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
−1,999 to 9,999 or −199.9 or 999.9 (decimal point position dependent on input type)
0 to 99 hrs 59 min or 0 to 99 min 59 s
4 patterns, 16 steps (possible to use up to 4 patterns with the communications function.)
Time or ramp setting method
±0.2% (±500 ms) of the set value
Temperature input:
Current/voltage input:
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Malfunction: 10 to 55 Hz, 10 m/s
Destruction: 10 to 55 Hz, 20 m/s
Malfunction: 200 m/s
Destruction: 300 m/s
Operating:
Storage:
Operating:
Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case:
Terminals:
Non-volatile memory (number of writings: 100,000 operations)
Approx. 170 g;
Adapter: approx. 10 g
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance: ENV50141:
Immunity Burst:
UL61010C-1, CSA 22.2 No. 61010-1
Conforms to EN61326-1: 2006, EN61010-1 (IEC61010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is
mounted.
(100 m/s
−10°C to 55°C (with no icing)/3-year warranty period: –10°C to 50°C
−25°C to 65°C (with no icing)
35% to 85%
IEC standard IP20
IEC standard IP00
2
2
2
min. (approx. 20G), 3 times each in 6 directions
min. (30G), 3 times each in 6 directions
(approx. 10G) applied to the relay)
250 ms
100 ms
2
2
(approx. 1G) for 10 min each in X, Y, and Z directions
(approx. 2G) for 2 hrs each in X, Y, and Z directions
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2: 4 kV contact discharge (level 2)
ENV50140:
EN61000-4-4: 2 kV power-line (level 3)
8 kV air discharge (level 3)
10 V/m (amplitude modulated, 80 MHz to 1 GHz)
(level 3)
10 V/m (pulse modulated, 900 MHz)
10 V (0.15 to 80 MHz) (level 3)
2 kV I/O signal-line (level 4)
E5CK
4