Wiring and Connections
3-4-2 Removing the Terminal Block
54
1, 2, 3...
Floor Ducts
Leave at least 200 mm between the wiring and the top of the duct, as shown in
the following diagram.
Conduits
Separate the CPM2A I/O lines, power and control lines, and power cables, as
shown in the following diagram.
The terminal block on the CPM2A CPU Unit can be removed. Use the following
procedure.
The terminal blocks on the Expansion Units and Expansion I/O Units cannot be
removed.
1. Loosen the black screws at the ends of the terminal block as shown in the
following diagram.
CPM2A I/O lines
CPM2A I/O lines
Control cables and
CPM2A power lines
Black screws
Control cables and
CPM2A power lines Power cables
Power cables
Black screws
Metal plate (iron)
200 mm min.
Section 3-4