SNT120CPK EATON CUTLER HAMMER, SNT120CPK Datasheet - Page 39

Shunt Trip

SNT120CPK

Manufacturer Part Number
SNT120CPK
Description
Shunt Trip
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of SNT120CPK

Operating Voltage
120VAC
For Use With
EG And JG Frame Series G Circuit Breakers
November 2008
NG-Frame
Product Description
CA08101001E
All Cutler-Hammer NG-Frame Circuit
Breakers by Eaton Corporation are
suitable for reverse feed use.
All NG-Frame circuit breakers are
HACR rated.
Typical NG-Frame Circuit Breaker
Technical Data and Specifications
Table 12-69. UL 489/IEC 60947-2 Interrupting Capacity Ratings
Circuit
Breaker
Type
NGS
NGH
NGC
1600 amperes is not a UL or CSA listed rating. 1200 amperes is the maximum UL and
CSA rating for NG.
For more information visit: www.eaton.com
Series G Molded Case Circuit Breakers
400 – 1200 Amperes
NG-Frame
Number
of Poles
2, 3, 4
2, 3, 4
2, 3, 4
240 (UL)
100
200
65
Interrupting Capacity (kA Symmetrical Amperes)
Volts ac (50/60 Hz)
220 – 240
I cu
100
200
85
I cs
100
100
85
380 – 415
I cu
100
50
70
I cs
50
50
50
480
100
50
65
600
25
35
65
690
I cu
20
25
35
I cs
10
13
18
12-39
12

Related parts for SNT120CPK