SNT120CPK EATON CUTLER HAMMER, SNT120CPK Datasheet - Page 115

Shunt Trip

SNT120CPK

Manufacturer Part Number
SNT120CPK
Description
Shunt Trip
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of SNT120CPK

Operating Voltage
120VAC
For Use With
EG And JG Frame Series G Circuit Breakers
November 2008
L-Frame
Product Description
CA08101001E
All Cutler-Hammer L-Frame Circuit
Breakers by Eaton Corporation are
HACR rated.
L-Frame circuit breakers are available
as individual components (Frame,
Trip Unit, Terminals), or factory
assembled complete breakers.
L-Frame circuit breakers with
non-interchangeable trip units
are suitable for reverse feed use.
CE marked.
Typical L-Frame Circuit Breaker
Technical Data and Specifications
Table 12-201. UL 489 Interrupting Capacity Ratings
Table 12-202. IEC 947-2 Interrupting Capacity Ratings
Circuit
Breaker
Type
LDB
LD
CLD
HLD, HLDB
CHLD
LDC, LDCB
CLDC
Circuit
Breaker
Type
LDB
LD
CLD
HLD, HLDB
CHLD
LDC, LDCB
CLDC
Utilization category A circuit breakers.
L/R = 8 milliseconds minimum.
2-pole circuit breaker or two poles of 3-pole circuit breaker. Incorporating Thermal-Magnetic trip
unit only.
100% rated breakers.
Current limiting.
Utilization category A circuit breakers.
L/R = 8 milliseconds minimum.
2-pole circuit breaker or two poles of 3-pole circuit breaker. Incorporating Thermal-Magnetic trip
unit only.
100% rated breakers.
For more information visit: www.eaton.com
Series C Molded Case Circuit Breakers
125 – 600 Amperes
L-Frame
Number
of Poles
2, 3
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
Number
of Poles
2, 3
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
Interrupting Capacity (kA rms Symmetrical Amperes)
Volts ac (50/60 Hz)
240
100
100
200
200
Interrupting Capacity (kA Symmetrical Amperes)
Volts ac (50/60 Hz)
240
I cu
100
100
200
200
65
65
65
85
85
85
I cs
100
100
100
100
85
85
85
277
415
I cu
100
100
45
45
45
70
70
100
100
480
35
35
35
65
65
I cs
45
45
45
70
70
75
75
600
25
25
25
35
35
50
50
690
I cu
20
20
20
25
25
35
35
I cs
10
10
10
13
13
18
18
Volts dc
125
250
I cu
20
20
20
20
Volts dc
250
22
22
25
30
I cs
10
10
10
10
12-115
12